*2 If indoor unit and the connected remote controller / remote sensor are all TU2C-Link models, TU2C-Link
communication will be performed automatically.
For Central control address (DN [03]), Indoor unit address (DN [13])
Remote controller
Communication type
Display order
U series
TU2C-LINK
····
⇔
0128
⇔
00Un
⇔
0001
⇔
···
TCC-LINK
····
⇔
0064
⇔
00Un
⇔
0001
⇔
···
Other than U series
TCC-LINK
····
⇔
0064
⇔
0099
⇔
0001
⇔
···
For Line address (DN [12])
Remote controller
Communication type
Display order
U series
TU2C-LINK
····
⇔
0128
⇔
00Un
⇔
0001
⇔
···
TCC-LINK
····
⇔
0030
⇔
00Un
⇔
0001
⇔
···
Other than U series
TCC-LINK
····
⇔
0030
⇔
0099
⇔
0001
⇔
···
For Group address (DN [14])
Remote controller
Communication type
Display order
U series
····
⇔
0002
⇔
00Un
⇔
0000
⇔
···
TU2C-LINK
TCC-LINK
Other than U series
TCC-LINK
····
⇔
0002
⇔
0099
⇔
0000
⇔
···
DN
Item
Description
At shipment
120 Defrost shift
0000: Unavailable
0001: Available
0001: Available
121 Draft prevention control 0000: Unavailable
0001: Available
0001: Available
1C1 Rotation operation
0000: Unavailable
0001: Available
0000: Unavailable
1C2 Rotation interval
0001: 1 day
to
0028: 28 days
0001: 1 day
1C3 Rotation lap time
0000: 0
to
0007: 70 minutes
0003: 30 minutes
1C9 Free Cooling ON Temp. -0015: -15°C
to
0029: 29°C
0016: 16°C
1CA Free Cooling OFF Temp. -0015: -15°C
to
0029: 29°C
0010: 10°C
1Cb
Free Cooling ON/OFF
differential Temp."
0000: 0
to
0010: 10°C
0002: 2°C
1C8 Free Cooling
0000: Unavailable
0001: Available
0000: Unavailable
*1 Display order of “00Un”and “0099” varies depending on remote controller models or communication types.