+4
+3
Tsc
Ta(˚C)
Normal control
Max. frequency is
restricted to approximately
the rated cooling frequency
Tsh
–3
–4
Ta(˚C)
Normal control
Max. frequency is
restricted to approximately
the rated heating frequency
No.
16
17
18
Item
Central control mode
selection
Energy-saving
control
Max. frequency cut
control
Outline of specifications
1)
Setting at the centerl controller side enables to select the
contents which can be operated on the remote controller
at indoor unit side.
1)
Selecting [AUTO] mode enables an energy-saving to be
operated.
2) When using the remote controller RBC-AMSU5 ,
"Energy saving operation" can be performed even in
cooling mode and heating mode.
3)
The setup temperature is shifted (corrected) in the range
not to lose the comfort ability according to input values of
various sensors.
4)
Data (Input value room temp. Ta, Outside temp. To, Air
volume, Indoor heat exchanger sensor temp. Tc) for
20 minutes are taken the average to calculate correction
value of the setup temperature.
5)
The setup temperature is shifted every 20 minutes, and
the shifted range is as follows.
In cooling time: +1.5 to – 1.0K
In heating time: –1.5 to +1.0K
1) This control is operated by selecting [AUTO] operation mode.
2) COOL operation mode:
It is controlled according to the
following figure if To < 28°C.
Remarks
3) HEAT operation mode:
It is controlled according to the
following figure if To > 15°C.
∗
In case of the wireless type, the display lamp does not
change but the contents are same. If operating an item
which is prohibited by the central control mode from the
remote controller, it is notified with the receive sound,
Pi, Pi, Pi, Pi, Pi (5 times).
19
DC motor
1) When the fan operation has started, positioning of the
stator and the rotor are performed.
(Moves slightly with tap sound)
2) The motor operates according to the command from the
indoor controller.
Notes)
• When the fan rotates while the air conditioner stops due to
entering of outside air, etc, the air conditioner may operate
while the fan motor stops.
• When a fan lock is found, the air conditioner stops, and an
error is displayed.
Check code [P12]