[P19 trouble]
Refer to the service manual of the outdoor unit.
Is operation of 4-way valve normal?
(Check the pipe temp., etc.
during cooling/heating operation.
Replace outdoor temperature sensors.
TE sensor
TS sensor
Indoor TC sensor
YES
NO
[F02 trouble]
Correct connection of connector.
Are characteristics of
TC sensor resistance value normal?
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
∗
Refer to TC Characteristics.
Replace TC sensor.
Replace indoor P.C. board (MCC-1643).
Correct connection of connector.
Are characteristics of
TCJ sensor resistance value normal?
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
∗
Refer to TCJ sensor
(Temperature-Resistance
value
characteristic
table)
Replace TCJ sensor.
Replace indoor P.C. board (MCC-1643).
YES
YES
YES
YES
NO
NO
NO
NO
[F01 trouble]
- 67 -