Installation Manual
–
35
–
35-EN
(Example) Group control for complex system
Line system
Indoor No.
After setup of
automatic
address
After setup
change of manual
address
(example of
random setup)
(example of address
setup change)
Address: 1-1-1
Address: 1-1-2
Address: 2-1-2
Address: 2-1-2
Address: 2-2-2
Address: 3-3-1
Indoor address
Line address
Group address
Procedure
example
Outdoor unit
<Single system> <Twin system>
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
The above address is set by the automatic addressing when the power is turned on. However, line
addresses and indoor addresses are set randomly. For this reason, change the setting to match
line addresses with indoor addresses.
1
■
Manual address setting
1
Push and hold menu button and [ ] setting button simultaneously for 10 seconds or more.
2
Push OFF timer button to con
fi
rm the selected indoor unit.
<Line address>
3
Push the menu button until the Code No.
fl
ashes. And using the [ ] [ ] buttons, specify the Code
No.
[12]
.
4
Push the menu button until the Set data
fl
ashes. And using the [ ] [ ] buttons, set a line address.
5
Push OFF timer button to con
fi
rm the Set data.
<Indoor unit address>
6
Push the menu button until the Code No.
fl
ashes. And using the [ ] [ ] buttons, specify the Code
No.
[13]
.
7
Push the menu button until the Set data
fl
ashes. And using the [ ] [ ] buttons, set an indoor unit
address.
8
Push OFF timer button to con
fi
rm the Set data.
<Group address>
9
Push the menu button until the Code No.
fl
ashes. And using the [ ] [ ] buttons, specify the Code
No.
[14]
.
10
Push the menu button until the Set data
fl
ashes. And using the [ ] [ ] buttons, set a group address.
If the indoor unit is individual, set the address to 0000. (header unit: 0001, follower unit: 0002)
11
Push OFF timer button to con
fi
rm the Set data.
12
When all the settings have been completed, push ON/OFF button to
fi
nish the settings. (Return to
the normal mode)