Installation Manual
–
32
–
32-EN
■
Remote controller sensor
The temperature sensor of the indoor unit senses
room temperature usually. Set the remote
controller sensor to sense the temperature around
the remote controller.
Select items following the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[32]
for the Code No. in Procedure
4
.
•
Select the following data for the set data in
Procedure
5
.
Set data
Remote controller sensor
0000
Not in use (Factory default)
0001
In use
When
fl
ashes, the remote controller sensor is
defective.
Select the set data [0000] (not in use) or replace
the remote controller.
■
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change
to TCC-Link.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[FC]
for the Code No. in Procedure
4
.
•
Select the set data [0000] (TCC-Link) in
Procedure
5
.
Set data
Communication type
0000
TCC-Link
0004
TU2C-Link (Factory default)
■
Fan speed setting when
thermostat-OFF in cooling mode
Set the fan speed when the room temperature
reaches the set temperature in the cooling mode.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[9A]
for the Code No. in Procedure
4
.
•
Select the following data for the set data in
Procedure
5
.
Set data
Fan speed when thermostat-OFF
in cooling mode
0000
Remote controller setting
0001
Extremely low speed (UL)
(Factory default)
■
8°C operation
Pre-heating operation can be set for cold regions
where room temperature drops to below zero.
Follow to the basic opreration procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
•
Specify
[d1]
for the Code No. in Procedure
4
.
•
Select the following data for the set data in
Procedure
5
.
Set data
8°C Operation setting
0000
None (Factory default)
0001
8°C Operation setting
■
Installing optional parts
When installing optional parts, data setup may be
required with remote controller.
Be sure to set the data, according to Installation
Manual for optional parts.
■
Information
The following functions require a connection with
the RBC-AMTU
***
and RBC-AMSU
***
remote
controller. For details, refer to the manual included
with the remote controller.
•
Individual unit selection during group operation
•
Individual setting of louver position (wind
direction)
•
Swing type setting
•
Louver lock (no swing) setting
•
Energy saving operation (Power saving
operation)
•
Noti
fi
cation of
fi
lter cleaning time
■
Others
The following functions can be used with this
model. Refer to the Service Manual for more
information.
•
Rotation / backup operation
•
Free cooling
•
Secondary heating
•
Power shift