10-4.Address Setup
(Manual setting from remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push
+
+
buttons simultaneously
for 4 seconds or more.
2
(
←
Line address)
Using the temperature setup
/
buttons, set to the CODE No.
3
Using timer time
/
buttons, set the line
address.
4
Push
button.
(OK when display goes on.)
5
(
←
Indoor unit address)
Using the temperature setup
/
buttons, set to the CODE No.
6
Using timer time
/
buttons, set 1 to the
line address.
7
Push
button.
(OK when display goes on.)
8
(
←
Group address)
Using the temperature setup
/
buttons, set to the CODE No.
9
Using timer time
/
buttons, set
to Individual,
to Header unit, and
to
Follower unit.
10
Push
button.
(OK when display goes on.)
11
Push
button.
Setup completes. (The status returns to the usual stop status.)
(Example of 2-lines wiring)
(Solid line: Wiring, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller group wiring.
Group address
Individual :
0000
Master
unit
:
0001
Sub
unit :
0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address → 1
Indoor unit address → 1
Group address → 1
1
2
2
2
1
2
2
2
2
1
<Operation procedure>
1 2 3 4 5 6 7 8 9 10 11
END
3, 6, 9
END
11
2, 5, 8
4, 7, 10
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER