Failure mode detected by indoor unit
Operation of diagnostic function
Judgment and measures
Check
code
Cause of operation
Status of air
conditioner
Condition
E03
No communication from remote
controller (including wireless) and
communication adapter
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check control wires of remote controller and
communication adapters.
• Remote controller LCD display OFF (Disconnection).
• Central remote controller [97] check code.
E04
The serial signal is not output from
outdoor unit to indoor unit.
• Miswiring of inter-unit wire
• Serial communication circuit trouble
of outdoor P.C. board
• Serial communication circuit trouble
of indoor P.C. board
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Outdoor unit does not completely operate.
• Inter-unit wire check, correction of miswiring.
• Check outdoor P.C. board. Correct wiring of P.C.
board.
2. When outdoor unit normally operates.
• Check P.C. board (Indoor receiving / Outdoor
sending).
E08
Duplicated indoor unit address
Stop
Displayed
when trouble is
detected
1.Check whether remote controller connection (Group /
Individual) was changed or not after power supply turned
on (Finish of group construction / Address check).
* If group construction and address are not normal when
the power has been turned on, the mode automatically
shifts to address setup mode. (Resetting of address)
L03
Duplicated indoor header unit
L07
There is group wire in individual
indoor unit
L08
Unset indoor group address
L09
Unset indoor capacity
Stop
Displayed
when trouble is
detected
1.Set indoor capacity (DN = 11).
L30
Abnormal input of outside interlock
Stop
Displayed
when trouble is
detected
1.Check outside devices.
2.Check indoor P.C. board.
P10
Float switch operation
• Float circuit, Disconnection,
Coming-off, Float switch contact
trouble
Stop
Displayed
when trouble is
detected
1.Trouble of drain pump.
2.Clogging of drain pump.
3.Check float switch.
4.Check indoor P.C. board.
P12
Indoor DC fan trouble
Stop
Displayed
when trouble is
detected
1.Position detection trouble.
2.Over-current protective circuit of indoor fan driving unit
operated.
3.Indoor fan locked.
4.Check indoor P.C. board.
P19
4-way valve system trouble
• After heating operation has started,
indoor heat exchangers temp. is
down.
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check 4-way valve.
2.Check 2-way valve and check valve.
3.Check indoor heat exchanger (TC / TCJ).
4.Check indoor P.C. board.
P31
Unit automatically stops while
warning is output to other indoor
units.
Stop
(Follower unit)
(Automatic
reset)
Displayed
when trouble is
detected
1.Judge follower unit while header unit is [E03], [L03], [L07]
or [L08].
2.Check indoor P.C. board.
F01
Coming-off, disconnection or short-
circuit of indoor heat exchanger temp.
sensor (TCJ)
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check indoor heat exchanger temp. sensor (TCJ).
2.Check indoor P.C. board.
F02
Coming-off, disconnection or short-
circuit of indoor heat exchanger temp.
sensor (TC)
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check indoor heat exchanger temp. sensor (TC).
2.Check indoor P.C. board.
F10
Coming-off, disconnection or short-
circuit of indoor room air temp. sensor
(TA)
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check indoor room air temp. sensor (TA).
2.Check indoor P.C. board.
F29
Indoor EEPROM trouble
• EEPROM access trouble
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check indoor EEPROM. (including socket insertion)
2.Check indoor P.C. board.
E10
Communication trouble between
indoor MCU
• Communication trouble between
fan driving MCU and main MCU
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check indoor P.C. board.
E18
Regular communication trouble
between indoor header and follower
units and between master and sub
units
Stop
(Automatic
reset)
Displayed
when trouble is
detected
1.Check remote controller wiring.
2.Check indoor power supply wiring.
3.Check indoor P.C. board.