Piping length/additional refrigerant volume
14.5
Air flow distribution
RAV-132UH-PE
RAV-162UH-PE
RAV-262UH-PE
RAV-362UH-PE
RAV-462UH-PE
l
The amount of refrigerant put into the outdoor unit at the factory is equivalent to the one that fills up 20m length of refrigerant pipe.
l
If the length of refrigerant pipe is 20m or less, addition of refrigerant at the installation site is unnecessary. If the length of the pipe
exceeds 20m, add the refrigerant R-22.
l
Overcharge or undercharge of refrigerant in the outdoor unit will cause malfunction of the compressor. The prescribed amount of
the replenishment of the refrigerant is shown in the table above.
The permissible amount of refrigerant is the prescribed amount ±50g.
l
For RAV-362AH8-PE and RAV-462AH8-PE, the length of pipe exceeds 30m the size of pipe at the gas side must be raised
one rank (eq 19.0
→
22.2).
MODEL
No. of discharge way
4-way
3-way
2-way
Air flow direction
A
B
C
D
A
B
C
A
B
RAV-132/162/262UH-PE
Air volume ratio (%)
30
30
30
10
33
33
33
50
50
RAV-362/462UH-PE
Air volume ratio (%)
40
40
10
10
40
40
20
50
50
Piping joint
Ceilling panel
Not to block the A and B
direction (longer side).
Air flow direction & volume ratio
5 m
(Note)
When installing more than one unit in the same
room keep a 5m distance between each unit.
Top view
Indoor
Unit
Piping length
less than (m)
20
Additional amount of refrigerant
at installation site (kg)
Recharge amount of interchange time (kg)
Model
(RAV-)
25
30
35
40
45
50
5
10
15
20
25
30
35
40
45
50
162AH-PE
Filled at
factory
0.15 0.35
1.35 1.45 1.5
1.6 1.75 1.95
262AH-PE
262AH8-PE
0.3
0.6
2.2 2.25 2.3 2.35 2.65 2.95
362AH8-PE
0.25 0.5 0.75 1.0 1.25 1.5
3.0 3.15 3.25 3.4 3.65 3.9 4.15 4.4 4.65 4.9
462AH8-PE
0.25 0.5 0.75 1.0 1.25 1.5
3.6
3.7
3.8
3.9 4.15 4.4 4.65 4.9 5.15 5.4