-40-
4.18 RAV-462AH8-PE
No.
PARTS NAME
TYPE
SPECIFICATIONS
1
Compressor
YH506JA
Output (Rated) 3.75kW, 2 pole, 3 phase, 380/415V, 50Hz
Winding resistance 2.29 at 20°C
2
Outdoor unit fan motor
SMF-230-63N-2
Output (Rated) 63W, 6 pole, 1 phase, 230V, 50Hz
SMF-230-39N-2
Output (Rated) 39W, 6 pole, 1 phase, 230V, 50Hz
3
Running capacitor for outdoor
fan motor
EEP2G405HQA114
AC 400V, 4 µF
4
Magnetic contactor
FMSA-1
AC 230V, 50Hz, Tripping current 12A, Resetting manual
5
High pressure switch
ACB-2TBO4W
Tripping pressure 30kg/cm²G Resetting
pressure 23kg/cm²G
6
Soleniod coil
CHV-AC240V
AC 220~240V
7
Crankcase heater
AC 240V, 58W
8
Outdoor unit sensor for
heat-exchanger temp.
Maximum input 15.5mA
°C
–12
10
67.5
21.3
9
Transformer for outdoor unit
FT-67
AC 187~264V
10
Fuse
5A
11
Sensor for cooling operation in low
ambient temperature
Maximum input 15.5mA
°C
–12
10
67.5
21.3
K
W
K
W
W
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807