7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19 35/24 137SKV-E 0.8 to 1.0 11 to 13 39 to 41 High High 77
167SKV-E 0.7 to 0.9 10 to 12 47 to 49 High High 89
condition(°C)
Tempeature
Heat exchanger
pipe temp.
Model name
Standard
Indoor
Outdoor
Compressor
RAS-
pressure
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/15 7/6 137SKV-E 2.7 to 2.9 43 to 45 0 to 2 High High 80
167SKV-E 2.5 to 2.7 39 to 41 0 to 2 High High 89
Tempeature
Heat exchanger
condition(°C)
pipe temp.