E6581738
- 25 -
4.2.6.
fd01
(Inverter operating status 1 (real time))
bit Function
0
1
Note
0
Failure FL
No output
Under in
progress
-
1 Failure
Not
tripped
Tripped
Trip status includes
rtry
and
the trip retention status are also
regarded as tripped statuses.
2
Alarm
No alarm
Alarm issued
-
3
Under voltage (
moff
) Normal Under
voltage
-
4
Motor selection (1 or 2)
(THR 2 selection)
Motor 1 (THR1)
Motor 2 (THR2)
THR1:
pt
= setting value,
vl
,
vlv
,
vb
,
thr
THR2:
pt
= 0,
f170
,
f171
,
f172
,
f173
5
PID control off
PID control
permitted
PID control
prohibits
-
6
Acceleration/deceleratio
n pattern selection (1 or
2)
Acceleration/dec
eleration pattern
1 (AD1)
Acceleration/dec
eleration pattern
2 (AD2)
AD1:
acc
,
dec
AD2:
f500
,
f501
7 DC
braking
OFF
Forced DC
braking
-
8
Jog run
OFF
Jog run
-
9
Forward / reverse run
Forward run
Reverse run
-
10 Run/stop
Stop
Run
-
11
Coast stop (ST = OFF)
ST=ON
ST=OFF
-
12 Emergency
stop
No emergency
stop status
Emergency
stop status
-
13
Standby ST=ON
Start-up process
Standby
Standby: Initialization
completed, not failure stop
status, not alarm stop status
(
moff
,
ll
forced stop),
ST=ON, and RUN=ON
14 Standby
Start-up
process
Standby
Standby: Initialization completed,
not failure stop status and not
alarm stop status (
moff
,
ll
forced stop)
15 (Undefined)
-
-
-
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgment.
4.2.7.
fd00
(Output frequency (real time))
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
-
fd22
(Feedback value of PID (real time)) ............................. Unit: 0.01Hz
-
fd16
(Estimated speed (real time))....................................... Unit: 0.01Hz
-
fd29
(Input power (real time)) ............................................... Unit: 0.01kW
-
fd30
(Output power (real time)) ............................................ Unit: 0.01kW