7. PROFIBUS Local/Remote Operation
The example below shows how to configure the VF-MB1 for local/remote operation.
<Terminal function>
F terminal ............ RUN command
R terminal............ Local (Terminal in this example) / PROFIBUS switching
VIA terminal ........ Operation frequency command
<Wiring>
<Parameter setting>
cmod
(command mode selection) = 0 (terminal board)
fmod
(frequency setting mode selection 1) = 1 (VIA)
f112
(input terminal selection 2 (R)) = 48 (Local/PROFIBUS control)
<Operation>
R-CC terminal open:
VF-MB1 is controlled as slave device of PROFIBUS.
R-CC terminal closed:
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the VIA signal input.
8. GSD file
As for acquisition of an GSD file for VF-MB1 and VF-S15, please contact your Toshiba
distributor.