E6582051
- 22 -
4.3.
ZSW Status Word Data
Bit Value
Name
Note
0
1
Ready To Switch-on
Power supply is switched on
0
Not Ready To Switch-on
-
1
1
Ready To Operate
Refer to control word, bit 1.
0
Not Ready To Operate
-
2
1
Operation Enabled
Drive follows set point.
(Refer to control word 1, bit 3)
0
Operation Disabled
-
3
1
Fault Present
Inverter tripped.
0
No Fault
Inverter is not tripped.
4
1
Coast Stop Not Activated
-
0
Coast Stop Activated (OFF 2)
"Coast Stop (OFF 2)" command is present.
5
1
Quick Stop Not Activated
-
0
Quick Stop Activated (OFF 3)
"Quick Stop (OFF 3)" command is present
6
1
Switching On Inhibited
Control word bit1 or 2 is set to 0
or fault trip has been acknowledged.
0
Switching On Not Inhibited
-
7
1
Warning Present
Drive still operational: Alarm in service parameter: No
acknowledgement.
0
No Warning
Alarm not present or alarm has disappeared again
8
1
Speed Error
Within Tolerance Range
Refer to section 4.3.1.
0
Speed Error
Out Of Tolerance Range
9
1
Control Requested
Inverter is controlled by PROFINET master.
0
No Control Requested
Inverter is controlled by another interface.
10
1
f Or n Reached Or Exceeded
Actual value
≥
Comparison value (setpoint)
0
f Or n Not Reached
-
11 ----
Device-specification
(Reserved.)
12 ----
Device-specification
(Reserved.)
13 ----
Device-specification
(Reserved.)
14 ----
Device-specification
(Reserved.)
15 ----
Device-specification
(Reserved.)