Toshiba PNE001Z Function Manual Download Page 1

 

 

E6582051

 

 

 
 
 
 

 
 
 
 
 

TOSVERT VF-S15 

 

PROFINET Option Function Manual 

 

PNE001Z 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

NOTICE 

1. Read this manual before installing or operating. Keep this manual on hand of the end 

user, and make use of this manual in maintenance and inspection.   

2. All information contained in this manual will be changed without notice. Please contact 

your Toshiba distributor to confirm the latest information. 

Summary of Contents for PNE001Z

Page 1: ...manual before installing or operating Keep this manual on hand of the end user and make use of this manual in maintenance and inspection 2 All information contained in this manual will be changed without notice Please contact your Toshiba distributor to confirm the latest information ...

Page 2: ...pecific 27 5 3 Telegram 102 Vendor specific 28 5 4 How to use 28 5 5 The overview of the VF S15 parameter 29 5 6 Access to the PROFIdrive parameter 34 5 7 PROFIdrive parameter PNU 35 5 8 Access to drive parameter 37 6 PROFIdrive acyclic parameter access 39 6 1 Example1 Read the PROFIdrive parameter 39 6 2 Example 2 Change the PROFIdrive parameter 40 6 3 Example 3 Read the VF S15 parameter 41 6 4 E...

Page 3: ... 8 4 Drive parameters Main menu Monitoring 53 8 5 Network parameters Main menu Network Setup 54 8 6 Administration Main menu Network Setup 55 8 7 TCP IP statistics Main menu Diagnostics 56 8 8 Mod statistics Main menu Diagnostics 56 8 9 Activation of JAVA7 57 9 Specifications 60 ...

Page 4: ...uture reference or drive interface inspection This manual describes the supported functions for the PNE001Z In conjunction with this manual the following manuals are supplied by Toshiba and they are essential both for ensuring a safe reliable system installation as well as for realizing the full potential of the PNE001Z TOSVERT VF S15 Instruction Manual E6581611 TOSVERT VF S15 communication option...

Page 5: ...t these errors may cause damage to physical property 2 1 Such things as injury burns or shock that will not require hospitalization or long periods of outpatient treatment 2 Physical property damage refers to wide ranging damage to assets and materials Meanings of symbols Marking Meaning of marking Indicates prohibition Don t do it What is prohibited will be described in or near the symbol in eith...

Page 6: ...t smoke or an unusual odor or unusual sounds immediately turn power off If the equipment is continued in operation in such a state the result may be fire Call your local sales agency for repairs Transportation installation Warning Prohibited Do not operate the drive if it is damaged or any component is missing Doing so could result in electric shock or fire Call your local sales agency for repairs...

Page 7: ...andatory Check PROFINET state using below status word bit when the option unit is deactivated by an unusual event such as an operating error power outage failure etc ZSW Status Word Bit 3 Fault Bit 7 Warning The communication error occurs when 1 as value or this value cannot be read Deactivated option unit may cause an accident if the PROFINET state is not checked Make sure that the operation sign...

Page 8: ... a distance of 20cm or more between the drive s power cable and the data transmission cable Or the drive might malfunction because of noise Insert a magnetic contactor or similar device between the drive and the power supply to ensure that power is turned off if an emergency stop command is entered through the network ...

Page 9: ...t PNE001Z also supports The PROFIdrive parameters channel 1 2 Modbus TCP The PNE001Z supports the following Modbus services 03 0x03 Read Holding Registers 06 0x06 Write Single Register 16 0x10 Write Multiple Registers 43 0x2B Read Device Identification 1 3 PROFINET and Ethernet Features The PNE001Z supports the following functions Automatic IP address assignment via DHCP and DCP Support of MRP Med...

Page 10: ...flash No connection to the PROFINET Controller Red flickering The option has detected a communication error err8 Red ON The option has detected a option module error e 23 The behavior of SF LED Network Status Color and behavior Meaning OFF The option does not have IP address or powered off Green Red blinking Power up testing Green flickering In combination with other LEDs DCP manual identification...

Page 11: ... LNK LEDs work as follows The behavior of LNK LED for ModbusTCP Link Activity Color and behavior Meaning OFF No link Green Blink Network Activity at 100 Mbps Green ON Link established at 100 Mbps Yellow Blink Network Activity at 10 Mbps Yellow ON Link established at 10 Mbps ...

Page 12: ...Size Value 1 User specific status information 1 byte Length of the block 2 1 byte Trip code 3 1 byte Profile 4 1 byte Drive version LSB 5 1 byte Drive version MSB 6 1 byte Software version 7 1 byte Communication network fault 8 1 byte Internal link fault 1 7 GSDML file As for acquisition of a GSDML file for VF S15 please contact your Toshiba distributor ...

Page 13: ...ecome damaged Do not use tool for the mounting removing of option The inverter and option can become damaged 2 1 1 Mounting of option Insert option into option adapter Note Mount option adapter to inverter after option insertion Insert the option straightly and slowly along the guide inside option adapter Follow this instruction the connecter can become damaged Remove the option connector Lock the...

Page 14: ...pushing the release tab Remove an option in the direction of arrow while pushing the release tab in the lower direction Connect attached grounding cable to grounding terminal of inverter Grounding terminal of inverter Grounding terminal of option adapter Recommended tightening torque 0 5N m Release tab Release tab ...

Page 15: ...apter Cable specifications Minimum Cat 5e Use equipotential bonding conductors Connector RJ45 no crossover cable Shield both ends grounded Twisted pair cable Maximum cable length 100 m 328 ft The following table describes the pin layout of RJ45 connecter Pin Signal 1 TD 2 TD 3 RD 4 5 6 RD 7 8 Fix a cable so that a communication connector may be not taken the weight of wire 8 1 Port L and Port R ...

Page 16: ...3 Installation Topology The PNE001Z support several wiring solutions Daisy Chain and or Star topology Ring topology Note The ring topology can only be used with a Media Redundancy Protocol MRP capable managed switch ...

Page 17: ...n 7 Communication option 8 Terminal board VIC 9 10 11 Pulse train input 12 13 14 sr0 0 f519 0519 Setting of acceleration deceleration time unit 0 1 0 01s unit after execution 0 2 0 1s unit after execution 0 0 3 f749 0749 Integrating wattmeter display unit selection 0 1 1kWh 1 1 10kWh 2 1 100kWh 3 1 1000kWh 4 1 10000kWh 1 f856 0856 Number of motor pole pair for communication 1 2 poles 2 4 poles 3 6...

Page 18: ...n c101 is set to 5 0 c103 C103 Communication time out condition selection 0 Disconnection detection 1 When communication mode enable Both cmod and fmod are set CANopen or communication option only 2 1 Driving operation 1 c154 C154 PROFIdrive JOG1 frequency 0 0 to 20 0Hz 5 0Hz c155 C155 PROFIdrive JOG2 frequency 0 0 to 20 0Hz 5 0Hz c156 C156 PROFIdrive Tmax 0 1 to 60 0s 10 0s c157 C157 PROFIdrive T...

Page 19: ...Output voltage 0 01 5 fc91 Alarm information 6 fd22 PID feedback value 0 01Hz 7 fd06 Input terminal board status 8 fd07 Output terminal status 9 fe36 VIB input 0 01 10 fe35 VIA input 0 01 11 fe37 VIC input 0 01 12 fd04 Input voltage DC detection 0 01 13 fd16 Estimated speed 0 01Hz 14 fd18 Torque 0 01 15 16 17 18 19 f880 Free notes 20 fd29 Input power 0 01kW 21 fd30 Output power 0 01kW 22 fe14 Cumu...

Page 20: ...dule c528 c531 C528 C531 Subnet Mask actual The subnet mask actual of the option module Refer to 3 3 2 Assigning IP addresses for the details c532 c535 C532 C535 Gateway address actual The gateway IP address actual of the option module Refer to 3 3 2 Assigning IP addresses for the details c536 C536 Ethernet Error Monitor of the Ethernet error 0 No error 1 PROFINET I O timeout 2 Network overload 3 ...

Page 21: ... name according to the following rules 1 The parameter is displayed by the hexadecimal number 2 One parameter shows an ASCII character 3 The relation between the device name and the parameter is as follows Example for Device Name VFS15 2004PM Chars No Parameter Character Ex ASCII Ex Set point Ex 1 c081 V 56H 86 2 c082 F 46H 70 3 c083 S 53H 83 4 c084 1 31H 49 5 c085 5 35H 53 6 c086 2DH 45 7 c087 2 ...

Page 22: ...arameter c504 IP mode Comments 0 The option uses the address defined in c505 c516 1 Don t use on PNE001Z 2 The option receives its address from a DHCP server Device name contains c081 c096 a valid name 3 The option receives its address from PROFINET controller Case of automatic switching of c504 IP mode to 3 DCP Needed conditions The device has a Station Name configuration and validation The devic...

Page 23: ...plies with PROFIdrive standard Corresponding PPO Type 3 Word PLC INV INV PLC PP0 1 STW ZSW PZD1 2 HSW HIW PZD2 PKW1 PKW2 PKW3 PKW4 PZD1 PZD2 PZD3 PZD4 PZD5 PZD6 INV Inverter PKW Parameter ID value PZD Process Data cyclically transferred STW Control word HSW Main setpoint ZSW Status word HIW Main actual value ...

Page 24: ... the input of the RFG is set to 0 7 1 Fault Acknowledge Fault reset 0 1 0 No meaning 8 1 JOG 1 ON Inverter drives with JOG 1 speed 1 c154 0 JOG 1 OFF Jogging stop if JOG 1 was previously ON Stop drive according to setting parameter of inverter 9 1 JOG 2 ON Inverter drives with JOG 2 speed 2 c155 0 JOG 2 OFF Jogging stop if JOG 2 was previously ON Stop drive according to setting parameter of invert...

Page 25: ...1 Switching On Inhibited Control word bit1 or 2 is set to 0 or fault trip has been acknowledged 0 Switching On Not Inhibited 7 1 Warning Present Drive still operational Alarm in service parameter No acknowledgement 0 No Warning Alarm not present or alarm has disappeared again 8 1 Speed Error Within Tolerance Range Refer to section 4 3 1 0 Speed Error Out Of Tolerance Range 9 1 Control Requested In...

Page 26: ...checks that the timer Tmax has not timed out and if the actual value is within the tolerance If both conditions are fulfilled ZSW Bit 8 is set 1 and the timer is stopped The figure shows ZSW 8 when Tolerance c157 is 50 and Tmax c151 is 3s Actual value Setpoint HIW 0x4000 HIW 0x3000 HIW 0x1000 HIW 0x0000 HIW HIW 0x2000 20s 25s 30s 15s Tolerance HIW HIW 50 Time ZSW Bit 8 Tmax 3s Tmax Tmax ...

Page 27: ...ZSW Bit 6 1 ZSW Bit 0 0 STW Bit 0 0 STW xxxx xxxx xxxx x110 ZSW Bit 0 1 STW xxxx xxxx xxxx x111 from any state FAULT STW Bit 7 1 ZSW Bit 5 0 from any state ZSW Bit 3 1 Power ON STW Bit 3 0 ZSW Bit 2 0 ZSW Bit 4 0 from any state A B C D STW Bit 0 0 ZSW Bit 1 0 from any state Frequency 0 STW Bit 3 1 ZSW Bit 1 1 STW Bit 2 0 STW Bit 1 0 ZSW Bit 2 1 A STW Bit 4 1 D ZSW Bit 8 1 MAINS OFF Jogging 1 or 2 ...

Page 28: ...g is set to STW in order 0000 0100 0000 0110 0x0406 READY TO SWITCH ON 0000 0100 0000 0111 0x0407 READY TO OPERATE 0000 0100 0111 1111 0x047F OPERATION 0000 0100 0111 1110 0x047E OFF1 ACTIVE Normal Stop 4 4 1 2 Example 2 30Hz Reverse running When the reverse operation 0xE000 is set to HSW 0xE000 is two s complement of the 0x2000 as the forward frequency reference 30Hz The Setup to STW is same as t...

Page 29: ...Status information 1 2 fd00 Output frequency 0 01Hz 3 fd03 Output current 0 01 4 fd05 Output voltage 0 01 5 fc91 Alarm information 6 fd22 PID feedback value 0 01Hz 7 fd06 Input terminal board status 8 fd07 Output terminal status 9 fe36 VIB input 0 01 10 fe35 VIA input 0 01 11 fe37 VIC input 0 01 12 fd04 Input voltage DC detection 0 01 13 fd16 Estimated speed real time value 0 01Hz 14 fd18 Torque 0...

Page 30: ... ID value PZD Process Data cyclically transferred PKE Parameter ID 1st and 2nd octet IND Sub index 3rd octet 4th octet is reserved PWE Parameter value 5th until 8th octet 5 2 Telegram 101 Vendor specific Corresponding PPO Type 2 Word PLC INV INV PLC PP0 1 Detailed behavior described in 5 6 to 5 8 PKW1 PKE 2 PKW2 IND 3 PKW3 PWE1 4 PKW4 PWE2 5 c001 c021 PZD1 6 c002 c022 PZD2 7 c003 c023 PZD3 8 c004 ...

Page 31: ...ou want to set 0xC400 to parameter fa06 set 1 fa06 to parameter c001 And Since 0 and 1 byte of the PZD1 supports the parameter c001 if 0xC400 is set up here 0xC400 will be set as fa06 Example 2 State monitoring When you want to monitor the output current set 3 FD03 to parameter c021 The value of the parameter fd03 specified as 0 and1 byte of the PZD1 with the parameter c021 is inputted VF S15 PNE0...

Page 32: ...Motor 2 THR 2 THR 1 pt setting value thr THR 2 pt 0 f170 f171 f172 f173 5 PI D control Normal operation PI D off 6 Acceleration decele ration pattern selection 1 or 2 AD2 selection Acceleration decel eration pattern 1 AD1 Acceleration dec eleration pattern 2 AD2 AD1 acc dec AD2 f500 f501 7 DC braking OFF Forced DC braking 8 Jog run OFF Jog run 9 Forward reverse run selection Forward run Reverse ru...

Page 33: ...le when Frequency reference is set up to 80Hz since the minimum unit is 0 01Hz 80 0 01 8000 0x1F40 Hex 5 5 4 fa50 Terminal output data from communication By setting up the data of the bit 0 1 of terminal output data fa50 from communication setting data OFF or ON can be outputted to the output terminal Please select the functional number 92 95 as the selection f130 f138 of the output terminal funct...

Page 34: ...p Run 11 Coast stop ST OFF ST ON ST OFF 12 Emergency stop No emergency stop status Emergency stop status 13 Standby ST ON Start up process Standby Standby Initialization completed not failure stop status not alarm stop status moff ll forced stop ST ON and RUN ON 14 Standby Start up process Standby Standby Initialization completed not failure stop status and not alarm stop status moff ll forced sto...

Page 35: ...inal board monitor Communication Number fe36 VIC terminal board monitor Communication Number fe37 These monitors can also be used as A D converters irrespective of the drive s control VIA VIC terminal board monitor is capable of reading the data from external devices in a range of 0 01 to 100 00 unsigned data 0x0000 to 0x2710 VIB terminal board monitor is capable of reading the data from external ...

Page 36: ...op after LL continuance time Dec Under stop Refer to f256 value 5 5 13 fd06 Input TB Status bit TB Name Function Parameter 0 1 0 F Input terminal function selection 1 f111 OFF ON 1 R Input terminal function selection 2 f112 2 RES Input terminal function selection 3 f113 3 S1 Input terminal function selection 4 f114 4 S2 Input terminal function selection 5 f115 5 S3 Input terminal function selectio...

Page 37: ...r PNU access 2 Change parameter value word for PNU access 6 Request parameter value array for PNU access or inverter parameter access 7 Change parameter value array for PNU access or inverter parameter access AK Response from PNE001Z to Master Response ID Function 0 No response 1 Transfer parameter value word 4 Transfer parameter value array 7 Task can not be executed followed by error number 0 Il...

Page 38: ... parameter c024 PNU 916 IND 4 the drive parameter c025 PNU 916 IND 5 the drive parameter c026 922 R Unsigned16 Telegram selection same as the drive parameter c152 1 100 101 102 923 R Unsigned16 List of all the parameters for signals 930 R Unsigned16 Operating mode 1 supports the speed control mode and the speed setpoint channel comprises RFG functionality 944 R Unsigned16 Fault message counter 947...

Page 39: ... 1 0 1 3 9 A Requirement PKW PZD PKE IND PWE 13 9A 00 00 00 00 00 00 Response Value 0x0065 101 13 9A 00 00 00 00 00 65 5 7 1 2 Example 2 Reading the PNU 964 IND 0 AK 6 Request parameter value array SPM 0 PNU 964 0x03C4 IND 0 PNE001Z ID PKE 0 1 1 0 0 0 1 1 1 1 0 0 0 1 0 0 6 3 C 4 Requirement PKW PZD PKE IND PWE 63 C4 00 00 00 00 00 00 Response Value 0x0190 PNE001Z ID 43 C4 00 00 00 00 01 90 ...

Page 40: ...mmunication number PKE 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 6 0 0 1 Requirement PKW PZD PKE IND PWE 60 01 00 03 00 00 00 00 Response Value 0x0001 Operation panel 40 01 00 03 00 00 00 01 5 8 1 2 Example 2 Reading the extended parameter f219 VIC input point 2 frequency AK 6 Request parameter value array SPM 0 PNU 1 IND 0x0219 f219 communication number PKE 0 1 1 0 0 0 0 0 0 0 0 0 0 0 0 1 6 0 0 1 Requireme...

Page 41: ...ter value array SPM 0 PNU 1 IND 0x0009 acc communication number PKE 0 1 1 1 0 0 0 0 0 0 0 0 0 0 0 1 7 0 0 1 Requirement acc 7 0 sec 70 0x0046 PKW PZD PKE IND PWE 70 01 00 09 00 00 00 46 Response 40 01 00 09 00 00 00 46 When the Acceleration time is set to 7 0 sec set the following value The unit of the Acceleration time is according to the parameter f519 7 0 0 1 70 0x0046 hexadecimal number Notes ...

Page 42: ...ss Byte 1 Attribute 0x10 Value 0x10 Parameter Address Byte 2 Number of Elements 0x01 Parameter Address Byte 3 Parameter number PNU High byte 0x03 Parameter Address Byte 4 Parameter number PNU Low byte 0xC4 Parameter Address Byte 5 Sub index IND High byte 0x00 Parameter Address Byte 6 Sub index IND Low byte 0x00 6 1 2 Response data table positive Field Description Value Request Header Byte 1 Reques...

Page 43: ...ue Byte 2 Number of Value 0x01 Parameter Value Byte 3 Values High byte 0x00 Parameter Value Byte 4 Values Low byte 0x00 Refer to section 6 5 6 2 2 Response data table positive Field Description Value Request Header Byte 1 Request Reference mirrored 0x01 Request Header Byte 2 Response ID 0x02 Positive 0x02 Request Header Byte 3 Axis mirrored 0x01 Request Header Byte 4 Number of Parameters 0x01 6 2 ...

Page 44: ...eter number Low byte 0xE8 Parameter Address Byte 5 VF S15 Parameter number High byte 0xFD Parameter Address Byte 6 VF S15 Parameter number Low byte 0x04 Refer to section 6 5 Parameter number is fixed to 0x03E8 1000 for accessing to VF S15 parameter 6 3 2 Response data table positive Field Description Value Request Header Byte 1 Request Reference mirrored 0x01 Request Header Byte 2 Response ID 0x01...

Page 45: ...1 Format 0x06 Parameter Value Byte 2 Number of Value 0x01 Parameter Value Byte 3 Value High byte 0x00 Parameter Value Byte 4 Value Low byte 0x07 Refer to section 6 5 Parameter number is fixed to 0x03E8 1000 for accessing to VF S15 parameter 6 4 2 Response data table positive Field Description Value Request Header Byte 1 Request Reference mirrored 0x01 Request Header Byte 2 Response ID 0x02 Request...

Page 46: ...ted may only be reset 0x07 Description element cannot be changed 0x09 No description data available 0x0B No operation priority 0x0F No text array available 0x11 Request cannot be executed because of operating state 0x14 Value impermissible 0x15 Response too long 0x17 Write Req Illegal format format of the parameter data is not supported 0x18 Number of values are not consistent 0x19 Axis DO non exi...

Page 47: ...on code The frame header returned by the VF S15 server is identical to that of the frame sent by the client 7 2 Drive Modbus servers The destination identifier Unit ID is used to access drive Modbus TCP servers Unit ID Modbus TCP server Accessible data 0 248 Inverter VF S15 Inverter parameter Device identification of inverter 251 Communication module PNE001Z Device identifications of module 7 3 Li...

Page 48: ...Byte Meaning 0 Function Code 03h 1 Starting Address Hi 2 Starting Address Lo 3 Number of Points Hi 0 4 Number of Points Lo 1 125 Response format Byte Meaning 0 Function Code 03h 1 Byte Count B 2 Number of Points 2 First Point Data Hi 3 First Point Data Lo B Last Point Data Hi B 1 Last Point Data Lo Exception response format Byte Meaning 0 Function Code 83h 1 Exception Code 01 Illegal Function 02 I...

Page 49: ...llegal Function 02 Illegal Data Address 03 Illegal Data Value 04 Slave Device Failure Notes As for the EEPROM parameter first the data is written to RAM after that the data is written to EEPROM Some EEPROM parameters cannot be changed during the inverter is running When write to EEPROM parameter that will change inverter status from stop to run the inverter must be in the state that it cannot run ...

Page 50: ...rting Address Lo 3 Number of Registers Hi 0 4 Number of Registers Lo 1 100 Exception response format Byte Meaning 0 Function Code 90h 1 Exception Code 01 Illegal Function 02 Illegal Data Address 03 Illegal Data Value 04 Slave Device Failure Notes As for the EEPROM parameter first the data is written to RAM after that the data is written to EEPROM Some EEPROM parameters cannot be changed during the...

Page 51: ...de 01 Basic 02 Regular 03 Extended 3 Conformity Level 2 4 More Follows 0 5 Next Object Id 0 6 Number Of Objects 3 for Basic 6 for Regular or Extended 7 Obj 0 Id Vendor Name 0 8 Obj 0 length 7 9 15 Obj 0 value TOSHIBA 16 Obj 1 Id ProductCode 1 17 Obj 1 length 13 18 30 Obj 1 value VFS15 2004PM 31 Obj 2 Id Version 2 32 Obj 2 length 5 33 37 Obj 2 value 11200 38 Obj 4 Id Product Name 4 Only for Regular...

Page 52: ...ject Id 0 6 Number Of Objects 3 for Basic 6 for Regular or Extended 7 Obj 0 Id Vendor Name 0 8 Obj 0 length 7 9 15 Obj 0 value TOSHIBA 16 Obj 1 Id ProductCode 1 17 Obj 1 length 7 18 24 Obj 1 value PNE001Z 25 Obj 2 Id Version 2 26 Obj 2 length 4 27 30 Obj 2 value 0201 Exception response format Byte Meaning 0 Function Code ABh 1 Exception Code 01 Illegal Function 02 Illegal Data Address 03 Illegal D...

Page 53: ...ated webserver of PNE001Z 8 1 Access to the webserver This web server can be accessed by the navigators listed below Microsoft Internet Explorer Version 7 0 or greater The navigator must support Java Virtual Machine because the factory loaded web server uses applets Startup the web browser and input IP address of the drive as the homepage address From your web browser default http password and log...

Page 54: ... to 3 main menus Home Monitoring Drive Monitor Drive parameters Network Setup Network Parameters Administration Diagnostics TCP IP Statistics Modbus Statistics If the screen does not appear well please try to return the magnification of IE7 to 100 ...

Page 55: ...uses the same structure Each main menu Monitoring Network Setup and Diagnostics contains each own sub menu Sub menus are displayed on the left side of web page 8 3 Drive Monitor Main menu Monitoring The state of the drive can be confirmed on this page ...

Page 56: ...s used to select a modify group or list of parameters The right column displays the parameters its Modbus address and its current value Set the parameters When you modify the drive parameter from the webserver please press the set button and input the PASSWORD The default password is USER Start the monitor Set the parameter ...

Page 57: ...E6582051 54 Set the parameters value Input the write value to popup window 8 5 Network parameters Main menu Network Setup The network parameters of the drive can be confirmed on this page ...

Page 58: ... Network Setup The web read password and web write password of the webserver can be modify on this page Press the Password button and enter the web write password After that press the Enter key Enter the new password and press the Save button ...

Page 59: ...E6582051 56 8 7 TCP IP statistics Main menu Diagnostics You can check TCP IP status on this page 8 8 Mod statistics Main menu Diagnostics You can check Modbus status on this page ...

Page 60: ...n of your internet browser We recommend using Internet Explorer If the version 1 8 25 or other 1 8 version are already installed on your computer you can install the 1 7 67 too 8 9 1 Activate JAVA1 7 version To configure your Java please do following instructions After activation of 1 7 67 you can close this window with OK ...

Page 61: ...E6582051 58 8 9 2 Delete temporary files If you had started a web server in the JAVA8 you will need to delete the temporary file with the following procedure OK to validate and close this window ...

Page 62: ...ername and password After the loading of Java application you will see bellow window Please select Execute After that you will see a new window please select Authorize the execution of the application with the requested version 1 7 67 and select Continue You will see the webserver correctly ...

Page 63: ... 4PKW and 6 PZD vendor format Telegram101 6 PZD vendor format Telegram102 Acyclic communication Reading the PROFIdrive parameter Reading writing the inverter parameters Configuration Configure by PROFINET master IP configuration mode Manual setup DCP DHCP Embedded Web server PROFINET IO classes Conformance Class B I M I M function 0 Modbus TCP Baud rate 10 100Mbps Full Half duplex Supported functi...