2. Function Outline
8
Alarm confirmation method and alarm priority
When an abnormality occurs in the process, a process alarm will be reported to OIS function.
This alarm is made based on the alarm grade.
The display style of a process alarm depends on an “Alarm confirmation method”.
“Alarm confirmation method” is specified in each tag. You can specify one method from
Type A, Type B, and Type C for each tag.
(1)Type A (It is recovered by the LO operation)
Blinking stops when CNF operation is done.
A state of alarm is held until LO operation is done even if it is recovered.
(2)Type B (It copes with the condition of the Process tag)
An unconfirmed alarm is held until CNF operation is carried out even if it is recovered.
(3)Type C (A change in a signal becomes an alarm)
It becomes an unconfirmed state of alarm at the time of the alarm occurrence, and becomes an
unconfirmed state of normality at the time of the recovery.
An alarm is confirmed by the CNF operation.
Refer to Appendix.1 “Alarm confirmation method” for the detailed movement of each alarm
confirmation method.
Alarm grade gives a grade to the alarm corresponding to the importance of the process alarm.
There are four kinds of “Warning”, “Minor ALM”, “Medium ALM”, and “Major ALM” for the
alarm grade.
Alarm grade can be registered independently in all the alarms which a tag has. Alarm priority
depends on the alarm grade and the confirmation status of the alarm.
Table2.2
Priority of the Process Alarm
Confirmed/Unconfirmed
Alarm grade
Indication color
Priority
Unconfirmed
Major ALM
Red blinking
1
Medium ALM
Purple blinking
2
Minor ALM
Yellow blinking
3
Normality/Rec
overy
Green blinking
4
Confirmed
Major ALM
Red lighting
5
Medium ALM
Purple lighting
6
Minor ALM
Yellow lighting
7
Normality
Green lighting
8
Summary of Contents for OIS-DS/Smart
Page 1: ...OIS DS SMART System Function Manual 6F8C1001 Toshiba Integrated Control System ...
Page 10: ...Safety viii ...
Page 18: ...1 Outline 4 ...
Page 24: ...2 Function Outline 10 Figure 2 4 Tag Group Display Figure 2 5 Point Display Screen ...
Page 25: ...2 Function Outline 11 Figure 2 6 Tag Search Screen Figure 2 7 Graphic Screen ...
Page 52: ...4 Software Package Configuration 38 ...
Page 54: ...5 Operating Conditions 40 ...
Page 58: ...Appendix 1 Alarm Confirmation Method 44 ...
Page 59: ......
Page 60: ...Industrial Systems Division 72 34 Horikawa Cho Saiwai Ku Kawasaki 212 8585 Japan ...