144-EN
143-EN
– 72 –
EN
¡
When executing a test run using
the interface P.C. board on the
outdoor unit
You can execute a test run by operating switches
on the interface P.C. board of the header outdoor
unit. “Individual trial”, which tests each indoor unit
separately, and “collective trial”, which tests all the
indoor units connected, are available.
<Individual test operation>
T
Starting operation
1
Set the running mode to “COOL” or “HEAT”
on the remote controller of the indoor unit to
be tested.
(The unit will run in the current mode unless
you set the mode otherwise.)
7-segment display
[A]
[B]
[U1]
[ ]
2
Set the rotary switches on the interface
P.C. board of the header outdoor unit:
SW01 to [16], SW02 and SW03 to the address
of the indoor unit to be tested.
SW
01
SW
02
SW
03
Indoor unit address
16 1 to 16
1
1 to 16
Set number of SW02
16 1 to 16
2
17 to 32
Set number of SW02 + 16
16 1 to 16
3
33 to 48
Set number of SW02 + 32
16 1 to 16
4
49 to 64
Set number of SW02 + 48
16 1 to 16
5
65 to 80
Set number of SW02 + 64
16 1 to 16
6
81 to 96
Set number of SW02 + 80
16 1 to 16
7
97 to 112 Set number of SW02 + 96
16 1 to 16
8 113 to 128 Set number of SW02 + 112
7-segment display
[A]
[B]
[ ]
L
Address display of the
corresponding indoor unit
[ ]
3
Push and hold SW04 for more than 10
seconds.
7-segment display
[A]
[B]
[ ]
L
Address display of the
corresponding indoor unit
[ ]
L
[FF] is displayed for 5
seconds.
NOTE
• The running mode follows the mode setting on the
remote controller of the target indoor unit.
• You cannot change the temperature setting during
the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after
turning the power on or stopping running.
T
Finishing operation
1
Set the rotary switches on the interface
P.C. board of the header unit back: SW01 to
[1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
<Collective trial>
T
Start operation
1
Set the rotary switches on the interface P.C. board of the header outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
When in “FAN” mode: SW01=[2], SW02=[9], SW03=[1].
7-segment display
[A]
[C ]
[H ]
[F ]
[B]
[ ]
[ ]
[ ]
2
Push and hold SW04 for more than 2 seconds.
NOTE
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display
[A]
[C ]
[H ]
[F ]
[B]
[ - C ]
[ - H ]
[ - F ]
T
Stop operation
1
Set the rotary switches on the interface P.C. board of the header unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]