58-EN
57-EN
– 29 –
(Unit: mm)
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size
Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
C
F
K
G
6.35
6.35 (±0.03)
6.45 (±0.03)
7
6
0.06 or less
0.50
9.52
9.52 (±0.03)
9.62 (±0.03)
8
7
0.08 or less
0.60
12.70
12.70 (±0.03)
12.81 (±0.03)
9
8
0.10 or less
0.70
15.88
15.88 (±0.03)
16.00 (±0.03)
9
8
0.13 or less
0.80
19.05
19.05 (±0.03)
19.19 (±0.03)
11
10
0.15 or less
0.80
22.22
22.22 (±0.03)
22.36 (±0.03)
11
10
0.16 or less
0.90
25.40
25.40 (±0.04)
25.56 (±0.04)
13
12
0.18 or less
0.95
28.58
28.58 (±0.04)
28.75 (±0.04)
13
12
0.20 or less
1.00
34.92
34.92 (±0.04)
35.11 (±0.04)
13
12
0.24 or less
1.20
38.10
38.10 (±0.05)
38.31 (±0.05)
15
14
0.27 or less
1.35
41.28
41.28 (±0.05)
41.50 (±0.05)
15
14
0.29 or less
1.45
44.45
44.45 (±0.05)
44.68 (±0.05)
17
14
0.31 or less
1.55
53.98
53.98 (±0.05)
54.22 (±0.05)
17
16
0.32 or less
1.80
Selection of pipe materials and sizes
¡
Selection of pipe materials
Materials : Phosphorus deoxidation seam-less pipe. Minimum wall thickness for R410A application.
Soft
Half hard or hard
OD (Inch)
OD (mm)
Minimum wall
thickness (mm)
ᅚ
ᅚ
1/4
ʺ
6.35 0.80
ᅚ
ᅚ
3/8
ʺ
9.52 0.80
ᅚ
ᅚ
1/2
ʺ
12.70 0.80
ᅚ
ᅚ
5/8
ʺ
15.88 1.00
ᅚ
3/4
ʺ
19.05 1.00
ᅚ
7/8
ʺ
22.22 1.00
ᅚ
1
ʺ
25.40
1.00
ᅚ
1-1/8
ʺ
28.58
1.00
ᅚ
1-3/8
ʺ
34.92
1.20
ᅚ
1-5/8
ʺ
41.28
1.45
ᅚ
1-3/4
ʺ
44.45
1.55
ᅚ
2-1/4
ʺ
53.98
1.80
¡
Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable
indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2-1, Table 2-2)
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable
indoor units differs based on the height difference between the indoor units.
• When the height difference between the indoor units is 15 m or less: Up to 200% of the capacity code
(Equivalent to HP) of the outdoor unit.
• When the height difference between the indoor units is over 15 m: Up to 105% of the capacity code.
• If MMU-UP
ᅷᅷᅷ
H is include in the system, total indoor capacity code must be between 70% and 105% of
outdoor unit capacity.
• If the system diversity is more than 135%, check the maximum number of indoor unit connections in table 2-1,
2-2, and then turn on DIP switch 3 of SW103 on the interface P.C. boards.
Table 1
Indoor unit
capacity rank
Capacity code
Equivalent to HP
Equivalent to
capacity
003
0.3
0.9
005
0.6
1.7
007
0.8
2.2
009
1
2.8
012
1.25
3.6
015
1.7
4.5
018
2
5.6
024
2.5
7.1
027
3
8.0
030
3.2
9.0
036
4
11.2
048
5
14.0
056
6
16.0
072
8
22.4
096
10
28.0
112
12
33.5
128
14
40.0