– 28 –
L20
—
—
Duplicated central control addresses
AI-NET, Indoor unit
L26
L26
Number of heat storage units connected
Too many heat storage units connected
I/F
L27
L27
Number of heat storage units connected
Error in number of heat storage units connected
I/F
L28
L28
—
Too many outdoor units connected
I/F
L29
L29
Number of IPDU (*1)
No. of IPDU error
I/F
L30
L30
Detected indoor unit address
Indoor unit outside interlock
Indoor unit
—
L31
—
Extended I/C error
I/F
P01
—
—
Indoor fan motor error
Indoor unit
P03
P03
—
Discharge temp. TD1 error
I/F
P04
P04
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
High-pressure SW system operation
IPDU
P05
P05
00:
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Phase missing detection / Power failure detection
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
I/F
P07
P07
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Heat sink overheat error
IPDU, I/F
P13
P13
—
Outdoor liquid back detection error
I/F
P15
P15
01:TS condition
02:TD condition
Gas leak detection
I/F
P17
P17
—
Discharge temp. TD2 error
I/F
P18
P18
—
Discharge temp. TD3 error
I/F
P19
P19
Detected outdoor unit number
4-way valve inverse error
I/F
P20
P20
—
High-pressure protective operation
I/F
P22
P22
0*:IGBT circuit
1*:Position detective circuit error
3*:Motor lock error
4*:Motor current detection
C*:TH sensor error
D*:TH sensor error
E*:Inverter DC voltage error (outdoor unit fan)
Outdoor unit fan IPDU error
Note: Ignore 0 to F displayed in “*” position.
IPDU
P26
P26
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
G-TR short protection error
IPDU
P29
P29
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Comp. position detective circuit system error
IPDU
P31
—
—
Other indoor unit error
(Group follower indoor unit error)
Indoor unit
A01
A01
Detected hot water module address
Flow switch protective operation
Hot water module
A02
A02
Detected hot water module address
Low temperature water error
Hot water module
A04
A04
Detected hot water module address
Plate type heat exchanger freezing protective operation
Hot water module
Check code
Check code name
Judging device
Wired remote controller display
Outdoor unit 7-segment display
Auxiliary code
55-EN
56-EN
Summary of Contents for MMW-AP0271LQ-E