– 27 –
F13
F13
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
TH sensor error
IPDU
F15
F15
—
Outdoor unit temp. sensor miscabling (TE, TL)
I/F
F16
F16
—
Outdoor unit pressure sensor miscabling (Pd, Ps)
I/F
F19
—
—
Hot water module TCJ2 (TF) sensor error
Hot water module
F22
F22
—
TD3 sensor error
I/F
F23
F23
—
Ps sensor error
I/F
F24
F24
—
Pd sensor error
I/F
F25
—
—
Hot water module TWI (TA) sensor error
Hot water module
F26
—
—
Hot water module TWO (TC2) sensor error
Hot water module
F29
—
—
Indoor unit other error
Indoor unit
F31
F31
—
Indoor unit EEPROM error
I/F
H01
H01
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor break down
IPDU
H02
H02
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Compressor trouble (lock)
IPDU
H03
H03
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
Current detect circuit system error
IPDU
H04
H04
—
Comp. 1 case thermo operation
I/F
H05
H05
—
TD1 sensor miswiring
I/F
H06
H06
—
Low pressure protective operation
I/F
H07
H07
—
Oil level down detective protection
I/F
H08
H08
01:TK1 sensor error
02:TK2 sensor error
03:TK3 sensor error
04:TK4 sensor error
05:TK5 sensor error
Oil level detective temp sensor error
I/F
H14
H14
—
Comp. 2 case thermo operation
I/F
H15
H15
—
TD2 sensor miswiring
I/F
H16
H16
01:TK1 oil circuit system error
02:TK2 oil circuit system error
03:TK3 oil circuit system error
04:TK4 oil circuit system error
05:TK5 oil circuit system error
Oil level detective circuit error
I/F
H25
H25
—
TD3 sensor miswiring
I/F
L02
—
—
Outdoor unit combination error
Hot water module
L03
—
—
Indoor unit centre unit duplicated
Indoor unit
L04
L04
—
Outdoor unit line address duplicated
I/F
L05
—
—
Duplicated indoor units with priority (Displayed in indoor unit with priority)
I/F
L06
L06
No. of indoor units with priority
Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority)
I/F
L07
—
—
Group line in individual indoor unit
Indoor unit
L08
L08
—
Indoor unit group / Address unset
Indoor unit, I/F
L09
—
—
Indoor unit capacity unset
Indoor unit
L10
L10
—
Outdoor unit capacity unset
I/F
L17
—
—
Outdoor unit type mismatch error
I/F
Check code
Check code name
Judging device
Wired remote controller display
Outdoor unit 7-segment display
Auxiliary code
53-EN
54-EN