– 7 –
3
System control of Hot Water Module
System able to be combined
The hot water module is connectable to only SMMS-i (Super Modular Multi system).
The system does not work when it connect to the MiNi-SMMS, SMMS (5,6 HP) and SHRM-i cannot be connected.
The Fresh Air Intake type and Air to Air Heat Exchanger with DX Coil cannot be connected with the same refrigerant system.
* When hot water module units and standard indoor units are not operated simultaneously.
▼
Capacity code of hot water module
• For the hot water module, the capacity code is decided at each model. (Table 1)
Table 1
The capacity code of the hot water module is different from the capacity code of the standard indoor unit.
NOTE
Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units (including hot water module) differs based on the height difference between the indoor units (including hot water module).
• When the height difference between the indoor units (including hot water module) is 15 m or less: Up to 115 % (including hot water module) of the capacity code (Equivalent to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit.
• When the height difference between the indoor units (including hot water module) is over 15 m: Up to 105 % (including hot water module) of the capacity code.
No.
Item
SMMS-i with
Hot Water Module connection
SMMS-i without
Hot Water Module connection
1
System capacity
48 HP
48 HP
2
No. of outdoor units connected
4
4
3
Indoor connection capacity
Max.
115 %
(including Hot Water Module)
135 %
Min.
65 %
(excluding Hot Water Module)
50 %
4
Hot Water Module connection capacity per refrigerant system
Max.
2 units and 50 % or less
-
5
Height
difference
Hight between outdoor and indoor units (including hot water module)
H1
H2 > 3 m
Upper outdoor units
50 m
See Figure 1
50 m
Lower outdoor units
30 m
30 m
H2
≤
3 m
Upper outdoor units
70 m
70 m
Lower outdoor units
40 m
40 m
Hight between indoor units (including hot water module)
H2, H4, H5
Indoor - Indoor
H2
Upper outdoor units
3 m (*40)
40 m
Lower outdoor units
10 m (*40)
Indoor - Hot water module
H5
Upper outdoor units
3 m (*40)
-
Lower outdoor units
10 m (*40)
-
Hot water module -
Hot water module
H4
Upper outdoor units
3 m
-
Lower outdoor units
3 m
-
Hot Water Module - Hot Water Module
Max. 3 m
-
Hot water module model
Capacity code
Equivalent to HP
Equivalent to capacity
MMW-AP0271LQ-E
2.5
7.1
MMW-AP0561LQ-E
5
14
13-EN
14-EN