29
SMMS 2-way Air Discharge Cassette Type
Installation Manual
EN-57
EN-58
F31
F31
—
1C
SIM
Indoor unit EEPROM error
I/F
H01
H01
01:
Comp. 1 side
02:
Comp. 2 side
03:
Comp. 3 side
IF
Compressor break down
IPDU
H02
H02
01:
Comp. 1 side
02:
Comp. 2 side
03:
Comp. 3 side
1d
Compressor trouble (lock)
IPDU
H03
H03
01:
Comp. 1 side
02:
Comp. 2 side
03:
Comp. 3 side
17
Current detect circuit system error
IPDU
H04
H04
—
44
Comp. 1 case thermo operation
I/F
H05
H05
—
—
TD1 sensor miswiring
I/F
H06
H06
—
20
Low pressure protective operation
I/F
H07
H07
—
d7
Oil level down detective protection
I/F
H08
H08
01:
TK1 sensor error
02:
TK2 sensor error
03:
TK3 sensor error
04:
TK4 sensor error
05:
TK5 sensor error
d4
Oil level detective temp sensor error
I/F
H14
H14
—
44
Comp. 2 case thermo operation
I/F
H15
H15
—
—
TD2 sensor miswiring
I/F
H16
H16
01:
TK1 oil circuit system error
02:
TK2 oil circuit system error
03:
TK3 oil circuit system error
04:
TK4 oil circuit system error
05:
TK5 oil circuit system error
d7
Oil level detective circuit error
I/F
H25
H25
—
—
TD3 sensor miswiring
I/F
L03
—
—
96
SIM
Indoor unit center unit duplicated
Indoor unit
L04
L04
—
96
SIM
Outdoor unit line address duplicated
I/F
L05
—
—
96
SIM
Duplicated indoor units with priority
(Displayed in indoor unit with priority)
I/F
L06
L06
No. of indoor units with priority
96
SIM
Duplicated indoor units with priority
(Displayed in unit other than indoor unit with
priority)
I/F
L07
—
—
99
SIM
Group line in individual indoor unit
Indoor unit
L08
L08
—
99
SIM
Indoor unit group/Address unset
Indoor unit, I/F
L09
—
—
46
SIM
Indoor unit capacity unset
Indoor unit
L10
L10
—
88
SIM
Outdoor unit capacity unset
I/F
Check code
Wireless remote controller
Check code name
Judging device
Wired remote
controller display
Outdoor unit 7-segment display
AI-NET central
control display
Sensor block display of receiving unit
Auxiliary code
Operation
Timer
Ready
Flash
Summary of Contents for MMU-AP0072WH
Page 36: ...DH91303401 ...