SMMS 2-way Air Discharge Cassette Type

Installation Manual

EN-1

EN-2

Contents

1

PRECAUTIONS FOR SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2

ACCESSORY PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

3

SELECTION OF INSTALLATION PLACE . . . . . . . . . . . . . . . . . . . . . . . . 6

4

INSTALLATION OF INDOOR UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5

DRAIN PIPING WORK  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

6

REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

7

ELECTRICAL WORK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

8

APPLICABLE CONTROLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

9

TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

10 MAINTENANCE  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
11 TROUBLE SHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
12 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Please read this Installation Manual carefully before installing the Air Conditioner.
• This Manual describes the installation method of the indoor unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.

ADOPTION OF NEW REFRIGERANT

This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional 
refrigerant R22 in order to prevent destruction of the ozone layer.

Thank you for purchasing this Toshiba air conditioner.
This Installation Manual describes the methods used to carry out the installation for the indoor unit.
For the installation of the outdoor unit, carry out the work by following the instructions in the Installation Manual 
provided with the outdoor unit.
This Installation Manual contains important information that complies with the “Machinery Directive” (Directive 2006/
42/EC) so read through it carefully to ensure that you understand its contents.
After completing the installation work, hand over this Installation Manual as well as the Owner’s Manual provided with 
the outdoor unit to the user, and ask the user to keep them in a safe place for future reference.

Provide a dedicated power outlet, which is separate from the one used for the outdoor unit, for supplying the power to 
the indoor unit.
Also, the Y-shape branching joint or branch header sold separately is required for the piping connections between the 
indoor unit and outdoor unit.
Select these joints or headers according to the piping system capacity.

Generic Denomination: Air Conditioner

Definition of Qualified Installer or Qualified Service Person

The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service 
person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the 
table below.

Agent

Qualifications and knowledge which the agent must have

Qualified 
installer

• The qualified installer is a person who installs, maintains, relocates and removes the air 

conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, 
maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, 
alternatively, he or she has been instructed in such operations by an individual or individuals 
who have been trained and is thus thoroughly acquainted with the knowledge related to these 
operations.

• The qualified installer who is allowed to do the electrical work involved in installation, 

relocation and removal has the qualifications pertaining to this electrical work as stipulated by 
the local laws and regulations, and he or she is a person who has been trained in matters 
relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, 
alternatively, he or she has been instructed in such matters by an individual or individuals who 
have been trained and is thus thoroughly acquainted with the knowledge related to this work.

• The qualified installer who is allowed to do the refrigerant handling and piping work involved 

in installation, relocation and removal has the qualifications pertaining to this refrigerant 
handling and piping work as stipulated by the local laws and regulations, and he or she is a 
person who has been trained in matters relating to refrigerant handling and piping work on the 
air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been 
instructed in such matters by an individual or individuals who have been trained and is thus 
thoroughly acquainted with the knowledge related to this work.

• The qualified installer who is allowed to work at heights has been trained in matters relating to 

working at heights with the air conditioners made by Toshiba Carrier Corporation or, 
alternatively, he or she has been instructed in such matters by an individual or individuals who 
have been trained and is thus thoroughly acquainted with the knowledge related to this work.

Original instruction

Summary of Contents for MMU-AP0072WH

Page 1: ... Installation manual Indoor Unit Model name 2 way Air Discharge Cassette Type MMU AP0072WH MMU AP0092WH MMU AP0122WH MMU AP0152WH MMU AP0182WH MMU AP0242WH MMU AP0272WH MMU AP0302WH MMU AP0362WH MMU AP0482WH MMU AP0562WH For commercial use ...

Page 2: ...be done ask a qualified installer or qualified service person to do them for you A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below Agent Qualifications and knowledge which the agent must have Qualified installer The qualified installer is a person who installs maintains relocates and removes the air conditioners made...

Page 3: ... relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified service person who is allowed to work at heights has been trained in matters relating...

Page 4: ...e indoor unit or service panel of the outdoor unit and do the work required Before carrying out the installation maintenance repair or removal work be sure to set the circuit breaker to the OFF position Otherwise electric shocks may result Place a Work in progress sign near the circuit breaker while the installation maintenance repair or removal work is being carried out There is a danger of elect...

Page 5: ...conditioner to malfunction Nitrogen gas must be used for the airtight test The charge hose must be connected in such a way that it is not slack If refrigerant gas has leaked during the installation work ventilate the room immediately If the leaked refrigerant gas comes in contact with fire noxious gas may be generated Electrical wiring Only a qualified installer 1 or qualified service person 1 is ...

Page 6: ...ter the refrigerating cycle To prevent charging an incorrect refrigerant and refrigerating oil the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant Accordingly the exclusive tools are required for the new refrigerant R410A For connecting pipes use new and clean piping designed for R410A and please care so ...

Page 7: ...der the unit installed that would be compromised by wetness If the drain has become blocked or when the humidity is over 80 condensation from the indoor unit will drip possibly causing damage to anything underneath In the case of the wireless type of system rooms with the inverter type of fluorescent lighting or locations exposed to direct sunlight The signals from the wireless remote controller m...

Page 8: ...ime of filter sign and To secure better effect of heating in APPLICABLE CONTROLS of this manual In case of wireless type Decide on the position where the remote controller is to be operated and where the unit is to be installed The wireless type can sense signals within a range of approximately 8 meters This distance serves as a general guideline It may be slightly more or slightly less depending ...

Page 9: ...rigerant pipe connecting port Liquid D Electric parts box L Refrigerant pipe connecting port Gas E Knockout square hole for auxiliary fresh air flange For Ø150 Sold separately M Drain pipe connecting port Be absolutely sure to use the flexible hose provided for the connection here F Knockout hole N Take in port of wires G Unit external dimension O Wireless signal sensor mounting area Sold separate...

Page 10: ...ld separately C Hanging bolt pitch K Refrigerant pipe connecting port Liquid D Electric parts box L Refrigerant pipe connecting port Gas E Knockout square hole for auxiliary fresh air flange For Ø150 Sold separately M Drain pipe connecting port Be absolutely sure to use the flexible hose provided for the connection here F Knockout hole N Take in port of wires G Unit external dimension O Wireless s...

Page 11: ... Liquid D Electric parts box L Refrigerant pipe connecting port Gas E Knockout square hole for auxiliary fresh air flange For Ø150 Sold separately M Drain pipe connecting port Be absolutely sure to use the flexible hose provided for the connection here F Knockout hole N Take in port of wires G Unit external dimension O Wireless signal sensor mounting area Sold separately H Hanging bolt M10 or W3 8...

Page 12: ...Use the pattern fastening screws M5 16 accessory When hanging a ceiling open the ceiling along the outside dimensions of the installation pattern Hanging bolt M10 or W3 8 4 pieces Nut M10 or W3 8 12 pieces Indoor unit Installation pattern Accessory Use the pattern fastening screws M5 16 accessory These screws are used only to fasten the installation pattern When mounting the ceiling panel use the ...

Page 13: ...e indoor unit is positioned 77 to 82 mm higher than the bottom surface of the ceiling panel All four corners 2 Check that the clearance between the outlet side shorter side of the indoor unit and ceiling panel is 25 mm 3 Check that the clearance between the outlet side longer side of the indoor unit and ceiling panel is 74 mm Hanging bolt M10 or W3 8 Nut M10 or W3 8 Procure hanging bolts and nuts ...

Page 14: ...ED AND APPLY A HEAT INSULATION SO AS NOT TO CAUSE A DEW CONDENSATION INAPPROPRIATE PIPING WORK MAY RESULT IN WATER LEAKAGE IN THE ROOM AND WET OF FURNITURE Provide the indoor drain piping with proper heat insulation Also be absolutely sure to provide the area where the pipe connects to the indoor unit with proper heat insulation Improper heat insulation will cause condensation to form Ensure that ...

Page 15: ... of the flexible hose provided into the drain pipe connecting port of the indoor unit as far as it will go Align the provided hose band with the end of the pipe connecting port and tighten it securely CAUTION Be absolutely sure to secure the soft end socket with the hose band provided and ensure that where the band is tightened is facing up Do not use the flexible hose provided with the hose bent ...

Page 16: ... the test run check that water drain is properly performed and water does not leak from the connecting part of the pipes When doing this also check that no abnormal sounds are heard from the drain pump motor Be sure to check draining also when installed in heating period When the electrical and wiring work has been completed Before attaching the panel pour some water by following the method shown ...

Page 17: ...N34 red Power supply wiring Tool for pouring water Bottle Water 1500 cc to 2000 cc Perform heat insulating As shown in the figure cover the flexible hose and hose band with the attached heat insulator up to the bottom of the indoor unit tightly Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat insulator of the drain connecting section Wr...

Page 18: ...se of flaring for R410A with the conventional flare tool pull it out approx 0 5 mm more than that for R22 to adjust to the specified flare size The copper pipe gauge is useful for adjusting projection margin size The sealed gas was sealed at the atmospheric pressure so when the flare nut is removed there will no whooshing sound This is normal and is not indicative of trouble Be absolutely sure to ...

Page 19: ...stalled an electric shock may be caused Be sure to use the cord clamps attached to the product Do not damage or scratch the conductive core and inner insulator of power and inter connecting wires when peeling them Use the power cord and Inter connecting wire of specified thickness type and protective devices required Never connect 220 V 240 V power to the terminal blocks etc for control wiring Oth...

Page 20: ...f the remote controller wiring and group remote controllers wiring CAUTION The remote controller wire Communication line and AC220 240V wires cannot be parallel to contact each other and cannot be stored in the same conduits If doing so a trouble may be caused on the control system due to noise etc Control wiring between indoor units and outdoor unit 2 core shield wire Wire size Up to 1000 m 1 25 ...

Page 21: ...with cord clamp attached to the electric parts box Do not apply tension to the connecting section of the terminal block Using the attached thermal insulation material seal the pipe connecting port Otherwise dewing may be caused Mount the cover of the electric parts box without pinching wires Mount the cover after wiring on the ceiling panel Pass the wires underneath the flashing protrusion of the ...

Page 22: ...roller unit Remote controller wire Field supply Terminal block for remote controller wiring of indoor unit Wiring between indoor and outdoor units NOTE An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the header unit Wiring example U1 U2 U1 U2 U3 U4 L1 L2 L3 N U5 U6 L N A B A B U1 U2 U3 U4 L1 L2 L3 N U5 U6 U1 U2 L N A B A B U1 U2 L N A B A B...

Page 23: ...t and repeat the procedure from the beginning No operation of the remote controller is accepted for a while after button is pushed While air conditioners are operated under the group control ALL is displayed first When is pushed the indoor unit number displayed following ALL is the header unit Display content varies with the indoor unit model 2 Each time you push button indoor unit numbers in the ...

Page 24: ...n it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room the detection temperature of heating can be raised Also use a circulator etc to circulate heat air near the ceiling Follow the basic operation procedure 1 2 3 4 5 6 For the CODE No in Procedure 3 specify 06 For the SET DATA in Procedure 4 select the SET DATA of Detection temp shif...

Page 25: ...y and the test run mode is established While the test run is underway TEST remains on the display 2 Push button 3 Using button select the operation mode COOL or HEAT Do not run the air conditioner in a mode other than COOL or HEAT The temperature controlling function does not work during test run The detection of error is performed as usual 2 4 3 1 5 4 After the test run push button to stop a test...

Page 26: ...ear the hooks at both ends and disengage the opening side hooks one at a time If the center panel holders refuse to slide loosen the screws a little more using the screwdriver Frame cover Screw Center panel holder Screw Center panel holder Center panel Center panel holder Frame cover Center panel holder Slide 1 2 1 2 This side drops down one step Center panel 2 3 Once you have checked that the hoo...

Page 27: ...lay disappears operate the air conditioner according to the following Confirmation of error history for confirmation Confirmation of error history When a trouble occurred on the air conditioner the trouble history can be confirmed with the following procedure The trouble history is stored in memory up to 4 troubles The history can be confirmed from both operating status and stop status 1 When push...

Page 28: ...re are two flashing LED Check code Wireless remote controller Check code name Judging device Wired remote controller display Outdoor unit 7 segment display AI NET central control display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash E01 Communication error between indoor unit and remote controller Detected at remote controller side Remote controller E02 Remote c...

Page 29: ... F01 0F ALT Indoor unit TCJ sensor error Indoor unit F02 0d ALT Indoor unit TC2 sensor error Indoor unit F03 93 ALT Indoor unit TC1 sensor error Indoor unit F04 F04 19 ALT TD1 sensor error I F F05 F05 A1 ALT TD2 sensor error I F F06 F06 01 TE1 sensor 02 TE2 sensor 18 ALT TE1 sensor error TE2 sensor error I F F07 F07 18 ALT TL sensor error I F F08 F08 1b ALT TO sensor error I F F10 OC ALT Indoor un...

Page 30: ... error 02 TK2 oil circuit system error 03 TK3 oil circuit system error 04 TK4 oil circuit system error 05 TK5 oil circuit system error d7 Oil level detective circuit error I F H25 H25 TD3 sensor miswiring I F L03 96 SIM Indoor unit center unit duplicated Indoor unit L04 L04 96 SIM Outdoor unit line address duplicated I F L05 96 SIM Duplicated indoor units with priority Displayed in indoor unit wit...

Page 31: ...ssing detection Power failure detection Inverter DC voltage error comp Inverter DC voltage error comp Inverter DC voltage error comp I F P07 P07 01 Comp 1 side 02 Comp 2 side 03 Comp 3 side IC ALT Heat sink overheat error IPDU I F P09 P09 Detected heat storage address 47 ALT No heat storage unit water error Heat storage unit P10 P10 Detected indoor unit address Ob ALT Indoor unit overflow error In...

Page 32: ... P31 47 ALT Other indoor unit error Group follwer indoor unit error Indoor unit b7 By alarm device ALT Error in indoor unit group AI NET 97 AI NET communication system error AI NET 99 Duplicated network adapters AI NET Check code Wireless remote controller Check code name Judging device Central control device indication Outdoor unit 7 segment display AI NET central control display Sensor block dis...

Page 33: ...N Authorized Representative TCF holder Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd Porsham Close Belliver Industrial Estate PLYMOUTH Devon PL6 7DB United Kingdom Hereby declares that the machinery described below Generic Denomination Air Conditioner Model type MMU AP0072WH MMU AP0092WH MMU AP0122WH MMU AP0152WH MMU AP0182WH MMU AP0242WH MMU AP0272WH MMU AP0302WH MMU AP0362WH...

Page 34: ... of R410A which is used in multi air conditioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and...

Page 35: ...ANGE STANDARD 0000 HIGH CEILING 1 0001 HIGH CEILING 3 0003 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to APPLICABLE CONTROLS in this manual Filter sign lighting time CODE NO 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE NO 01 NO CHANG...