– 24 –
EN
4
Push the menu button to make Code No. [
]
flash. Change Code No. [
] with [
] [
]
setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
] with
[
] [
] setting button.
6
Push OFF timer button to complete the set up.
• To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode).
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit, repeat
from Procedure
1
.
Filter sign setting
According to the installation condition, the filter sign term
(Notification of filter cleaning) can be changed. Follow to
the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[01]
for the Code No. in Procedure
4
.
• For the set data in Procedure
5
, select the set data of
filter sign term from the following table.
• The filter sign may be unavailable depending on the
remote controllers.
External static pressure
settings
To set the external static pressure, refer to the "Fan
characteristics" in
6 Duct design
.
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[5d]
for the Code No. in procedure
4
.
• For the set data of procedure
5
, select a set data of
the external static pressure to be set up from the
following table.
Remote controller-less setting
Change the external static pressure setting with the DIP
switch on the P.C. board.
• Once the Set data has been changed, though it can
be to reset it to 0000 (factory default), it need
changing using remote controller (sold separately).
After setting has been completed, restart the air
conditioner.
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set the
data of Code No. [5d] to “0000”.
Set data
Filter sign term
0000
None
0001
150 H
0002
2500 H
(Factory default)
0003
5000 H
0004
10000 H
Set data
External static pressure
0000
10Pa
Standard (Factory default)
0001
20Pa
High static pressure 1
0003
30Pa
High static pressure 2
0004
40Pa
High static pressure 3
0006
50Pa
High static pressure 4
SW501-1
OFF
ON
OFF
ON
SW501-2
OFF
OFF
ON
ON
Set data
0000
Factory
default
0001
0003
0006
SW501-1
MCU (IC501)
SW501-2
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[06]
for the Code No. in Procedure
4
.
• For the set data in Procedure
5
, select the set data of
shift value of detection temperature to be set up from
the following table.
Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor to
sense the temperature around the remote controller.
Select items following the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[32]
for the Code No. in Procedure
4
.
• Select the following data for the set data in
Procedure
5
.
When
flashes, the remote controller sensor is
defective.
Select the set data [0000] (not in use) or replace the
remote controller.
Group control
In a group control, a remote controller can control up to
maximum 8 or 16 units. (Depending on the outdoor
unit.)
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to “8 Electrical
connection” in this Manual.
• Wiring between indoor units in a group is performed in
the following procedure.
• Connect the indoor units by connecting the remote
controller wires from the remote controller terminal
blocks (A, B) of the indoor unit connected with a
remote controller to the remote controller terminal
blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
Set data
Detection temperature shift value
0000
No shift
0001
+1 °C
0002
+2 °C
(Factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
Set data
0000
0001
Remote controller
sensor
Not in use
(Factory default)
In use
47-EN
48-EN