58
7-3-4. Snowfall fan control
Operation
An external snowfall signal turns on the outdoor unit fan.
The input signal is recognized during its rising / falling phase.
(After reaching the top / bottom of the rising / falling edge, the signal must remain there for at least 100 ms.)
7-3-5. External master ON / OFF control
Operation
The system is started / stopped from the outdoor unit.
The input signal is recognized during its falling phase. (After reaching the bottom of the falling edge, the signal must
remain there for at least 100 ms.)
CAUTION
(1) Do not turn on the COOL (SW1) and HEAT (SW2) terminals simultaneously.
(2) Be sure to provide a contact for each terminal.
External signal: No-voltage pulse contact
Terminal
Input signal
Operation
COOL
(SW1)
Snowfall fan control
(Turns on outdoor
unit fan)
Normal operation
(Cancels control)
Terminal
Input signal
Operation
COOL
(SW1)
Turns on all indoor
units
HEAT
(SW2)
Turns off all indoor
units
Outdoor unit
COM
Outdoor unit
interface PCB
Optional PCB
Connection
cable
Locally procured
Snowfall sensor
Shield
wire
7
1
J
P
9
0
5
N
C
TB1
COOL
HEAT
SW1
SW1: Snowfall detection switch (snowfall sensor)
ON
OFF
ON
OFF
Outdoor unit
COM
Outdoor unit
interface PCB
Optional PCB
Connection
cable
Locally procured
Shield
wire
7
1
J
P
2
1
5
N
C
TB1
COOL
HEAT
SW1
SW1: Operation input switch
SW2: Stop input switch
SW2
ON
OFF
ON
OFF