Check code name
Cause
Check code
Trouble concerning high-pressure
SW
1.
High-pressure SW trouble
2.
S
ervice valve closed
3.
P
D sensor trouble
4.
Indoor/outdoor fan trouble
5.
Indoor/outdoor PMV choke
6.
Indoor/outdoor heat exchanger clogging, air short circuit
7.
SV2 circuit trouble
8.
SV4 circuit trouble
9.
SV5 circuit trouble
10. Discharge line check valve malfunction 11
. Refrigerant overcharge
Note) High-pressure SW is
normally closed. (B contact)
Does high-pressure SW
operate?
Are parts of high-
pressure SW normal?
Is service valve fully
opened?
Are characteristics of high-pressure sensor
normal?
Does cooling outdoor fan normally operate?
Is there any
interference of heat-
exchanging of outdoor unit? 1. Heat exchanger clogging
2.
A
ir short circuit
Is there any crack or coming-of
f of fan?
Connector connection, fan IPDU, fan motor
, wiring
Connectors: PMV1: CN300
Is circuit cabling
normal?
Check parts.
Failure
Replace
Check and correct
cabling.
Open service valve
fully
.
Replace the high-
pressure sensor
.
Repair failure parts.
Repair outdoor PMV
.
Eliminate the
interference.
Check
A3-IPDU P
.C. board.
Failure
replace
(B) Cooling operation
Cooling
T
o (B)
Heating
T
o (C)
Reset power supply
, and start a test
operation corresponded to the season.
Is outdoor PMV normal? 1. Connector connection
2. Cabling
3. Coil
4. V
alve body
5. Outdoor I/F P
.C. board
Ye
s
Ye
s
Ye
s
No
No
Ye
s
No
Ye
s
No
No
No
No
No
Ye
s
No
Ye
s
Ye
s
Ye
s
Ye
s
Ye
s
Ye
s
No
No
(C)
(A)
Is SV2 circuit normal?
Is SV4 circuit normal?
Does heating
indoor fan normally
operate?
Are connector
connection, condenser
,
fan motor and fan
normal?
Is connector connection
and coil normal?
Is there clogging
on any valve?
Are
characteristics
of
T
C2 and
TCJ sensor
resistance value
normal?
Is indoor PMV
normal?
Is SV5 circuit
normal?
(Check it using the miswiring check function of the outdoor unit.)
Are any indoor units of dif
ferent refrigerant
line connected?
Is there any
interference of heat-
exchanging of indoor unit?
1. Filter clogging
2. Heat exchanger clogging
3.
A
ir short circuit
Repair SV2 circuit.
Repair SV4 circuit.
(Coil failure clogging,
disconnection of
wiring, etc.)
Repair failure parts.
Repair failure parts.
Eliminate the
interference.
Replace PMV body
.
Check and correct the
wiring.
Replace
TC2 and/or
TCJ sensor
.
Repair failure parts;
connector connection,
cabling, coil installation,
clogging, etc
Refrigerant overcharge,
clogging, pipe
breakage, abnormal
overload condition
Check indoor P
.C. board.
Failure
Replace
Heating operation
Refrigerant overcharge, clogging, pipe breakage, abnormal overload condition
Coil failure clogging,
disconnection of wiring, etc.