7-3-2. Power peak-cut control (standard)
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch (ON as long as target power peak-cut control has been reached or
exceeded, normally OFF)*1
SW2: Power peak-cut control OFF switch (OFF as long as target power peak-cut control has not been reached or
exceeded, normally ON)*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
Do not turn on SW1 and SW2 simultaneously.
* Be sure to provide a contact for each terminal.
Power peak-cut control settings
Two-core cable support
It allows ON / OFF power peak-cut control to be implemented using a power peak-cut control ON input (SW1)
alone, provided that the J20 jumper wire on the interface P.C. board of the outdoor unit has been removed.
Power peak-cut control P.C.
board
SW1
SW2
L1
Interface P.C. board of outdoor unit
N
O
1
t
i
B
7
0
W
S
F
F
O
1
t
i
B
7
0
W
S
Power peak-cut control ON
signal received
ON
OFF
ON
0 % (forced stop)
60 % capacity (upper limit regulated)
Power peak-cut control OFF
signal received
OFF
ON
OFF
100 % (normal operation)
100 % (normal operation)
Outdoor unit
L1: Display lamp ensuring power peak cut control
Locally procured
Outdoor unit
interface PCB
CN513
SW07
Bit 2 OFF
Connection cable
Optional PCB
Display
relay
TB1
TB2
PJ17
COM
ON
OFF
COM
[ON]
[OFF]
[OPERATION]
Shield
wire
Power
supply
L1
SW1
SW2
SW1
SW2
Shield
wire
For SW1 and SW2, be sure to provide no-
voltage contacts for each terminal.
The input signals of SW1 and SW2 may be pulse
input (100 msec or more) or continuous make.
Outdoor unit
L1: Display lamp ensuring power peak cut control
Locally procured
Outdoor unit
interface PCB
CN513
SW07
Bit 2 OFF
Connection cable
Optional PCB
Display
relay
TB1
TB2
PJ17
COM
ON
OFF
COM
[ON]
[OFF]
[OPERATION]
Shield wire
Power
supply
L1
SW1
Shield wire
J20 Cut