E6581467

 

1. Scope 

 

1.1. Overview 

L

ON

W

ORKS

 technology is a network control system concept developed by Echelon Corporation, 

L

ON

W

ORKS

 network provides Local  Operating  Network that is superior in the distributed control. it is 

featured by peer to peer communication between the L

ON

W

ORKS 

nodes. This L

ON

W

ORKS

 option is 

equipped with the L

ON

W

ORKS

 Smart Transceiver (Neuron

 

Chip) and LonTalk

 

protocol in its firmware. 

This network has following features. 

1. Features the merit of distributed control. It enables to configure the network without Host computer. 

2. The free topology wiring supported by the TP/FT-10 channel type accommodates bus, star, loop, 

or several combinations of these topologies. 

3. Network construction tools are commercially available, and desirable network environment can be 

designed.  

4. Products of the other manufacturer can also be laid out by open and non-exclusive network. 

 

 

1.2. System 

configuration 

Number of connected units to the router: 63 nodes at maximum

LIU005Z

VF-S11

Free topology: 63 units connected at maximum

Host computer

Router

LIU005Z

- The free topology wiring example

means a node

Termination

resistor

VF-S11

- Network configuration example

Complex topology can be configured.

Router

Router

 

 

- 4 - 

Summary of Contents for LONWORKS option unit

Page 1: ...NOTICE 1 Read this manual before installing or operating the LONWORKS option unit Keep it in a safe place for reference 2 All information contained in this manual are subject to change without notice Please confirm the latest information on TOSVERT series web site www inverter co jp ...

Page 2: ...range to network variables Otherwise the motor may suddenly start stop and that may result in injuries Prohibited Use an additional safety device with your system to prevent a serious accident due to the network malfunctions Usage without an additional safety device may cause an accident Set up Communication error trip function see below to stop the inverter when the option unit is deactivated by ...

Page 3: ...Speed in min 1 14 4 4 9 nciNmlFreq Nominal Motor Frequency 14 4 4 10 nciRampUpTm Ramp Up Time 15 4 4 11 nciRampDownTm Ramp Down Time 15 4 4 12 nciDrvSpeedScale Default value for nviDrvSpeedScale 15 4 5 Input network variables 16 4 5 1 nviDrvSpeedStpt Drive Speed Setpoint 16 4 5 2 nviDrvSpeedScale Drive Speed Setpoint Scaling 16 4 5 3 nviInvSetFreq Frequency Setpoint 16 4 5 4 nviEmergOverride Emerg...

Page 4: ...E6581467 5 1 Procedure 22 5 2 Binding 22 5 3 Option unit reset method 22 5 4 Communication health management 23 6 Specifications 24 3 ...

Page 5: ...igure the network without Host computer 2 The free topology wiring supported by the TP FT 10 channel type accommodates bus star loop or several combinations of these topologies 3 Network construction tools are commercially available and desirable network environment can be designed 4 Products of the other manufacturer can also be laid out by open and non exclusive network 1 2 System configuration ...

Page 6: ...uit terminal is attached Otherwise it may lead to electric shocks Mandatory Operate Service switch using the non conductive stick When it is operated with a conductive stick Otherwise it may lead to electric shocks 2 3 Use of RS485 communication port RS485 port is useful for RS485 serial communication option USB001Z or Remote Keypad RKP002Z Refer to the inverter instruction manual for details N B ...

Page 7: ...n program is abnormal If the same indication appears after resetting the power it needs to be repaired 5 LED flashes every 1 second This is a normal action of the Unconfigured device If the device is not Unconfigured Internal application program is broken It needs to be repaired 6 LED momentarily turns ON then continues to be OFF When the program is in the condition of Configures status LED moment...

Page 8: ...me fh Maximum frequency ul Upper limit frequency ll Lower limit frequency Do not change these parameters because the LONWORKS option unit using them cmod Command mode selection fmod Setpoint mode selection Local command cmod and setpoint fmod are used until receiving them from LONWORKS network f111 f112 Logic input terminal function Set proper value if use See the inverter instruction manual f603 ...

Page 9: ...esistor between P24 terminal and setpoint potentiometer because this option has no PP 10V terminal Command Setpoint Control Terminal Operation Panel Serial Comm LONWORKS Internal potentiometer VIA VIB Operation Panel Serial Comm LONWORKS UP DOWN VIA VIB Serial Comm LONWORKS cmod fmod Logic input 48 SC LC Network cancel switch Block diagrams 0 1 2 3 4 5 6 0 1 2 1 0 1 0 Serial Comm LONWORKS 1 After ...

Page 10: ...ale SNVT_lev_percent nvoDrvPwr SNVT_power_kilo nvoDrvCurnt SNVT_amp nvoDrvVolt SNVT_volt nvoDrvRunHours SNVT_time_hour Configuration Properties nciLocation SNVT_str_asc nciPwUpOutTm SNVT_time_sec nciRcvHrtBt SNVT_time_sec nciSndHrtBt SNVT_time_sec nciMinOutTm SNVT_time_sec nciMaxSpeed SNVT_lev_percent nciMinSpeed SNVT_lev_percent nciNmlSpeed SNVT_rpm nciNmlFreq SNVT_freq_hz nciRampUpTm SNVT_time_s...

Page 11: ...pTm SNVT_time_sec 0 1s 10 0s 12 nciRampDownTm SNVT_time_sec 0 1s 10 0s 13 nciDrvSpeedScale SNVT_lev_percent 0 005 100 000 14 nviDrvSpeedStpt SNVT_switch 0 5 1 0 0 1 15 nviDrvSpeedScale SNVT_lev_percent 0 005 nciDrvSpeedScale 16 nviInvSetFreq SNVT_freq_hz 0 1Hz 3276 7Hz Invalid 17 nviEmergOverride SNVT_hvac_emerg binary EMERG_NORMAL 18 nviDrvReset SNVT_state boolean 19 nvoDrvSpeed SNVT_lev_percent ...

Page 12: ...the object the alarms are reported again as they are detected N B This option does not use the object ID so it works according to the request in spite of received value of object ID N B In case that receiving the request other than above this option unit sets 1 to invalid_request bit of nvoStatus output network variable 4 3 2 nvoStatus Object Status SNVT type SNVT_obj_status 93 This is the variabl...

Page 13: ... 300 0 the internal value is limited to 300 0 sec Unit 0 1 sec Default value 0 0 sec 4 4 3 nciRcvHrtBt Receive Heartbeat Time SNVT type SNVT_time_sec 107 It is used to control the maximum period of time that elapses after the last update of the network variables nviDrvSpeedStpt nviDrvSpeedScale nviInvSetFreq before detecting the network malfunction and initializing the command and setpoint values ...

Page 14: ...st variable Refer to 5 4 Communication health management for details Valid range 0 0 to 6553 4 sec Unit 0 1s Default value 0 5 sec Setting 0 0sec disables transmission limitation 4 4 6 nciMaxSpeed Maximum Speed SNVT type SNVT_lev_percent 81 It is used to define the maximum speed of the inverter output The value is entered as a percentage of nominal frequency nciNmlFreq The value of the maximum spe...

Page 15: ... running with unexpected speed Prohibited 4 4 8 nciNmlSpeed Nominal Motor Speed in min 1 SNVT type SNVT_rpm 102 It is used to provide the nominal speed of the inverter output in min 1 This value is not used in the option Valid range 0 to 65534 min 1 Unit 1 min 1 Default value 1800 min 1 4 4 9 nciNmlFreq Nominal Motor Frequency SNVT type SNVT_freq_hz 76 This configuration property is used to provid...

Page 16: ... Time SNVT type SNVT_time_sec 107 It determines the ramp down time of the motor Valid range 0 1 to 3200 0 sec Unit 0 1 sec Default value 10 0 sec N B By editing this variable this option unit changes the inverter parameter dec automatically 4 4 12 nciDrvSpeedScale Default value for nviDrvSpeedScale SNVT type SNVT_lev_percent 81 It is used as the default value for nviDrvSpeedScale When this option ...

Page 17: ...nded 4 5 2 nviDrvSpeedScale Drive Speed Setpoint Scaling SNVT type SNVT_lev_percent 81 This input network variable provides scaling for nviDrvSpeedStpt Negative values indicate a motor direction in reverse Valid range 163 840 to 163 830 Unit 0 005 Default value nciDrvSpeedScale Default value will be adopted at power up and in case of not receiving an update of nviSpeedStpt nviDrvSpeedScale or nviI...

Page 18: ...EMERG_DEPRESSURIZE Emergency depressurize mode 3 EMERG_PURGE Emergency purge mode 4 EMERG_SHUTDOWN Emergency shutdown mode 5 EMERG_FIRE Emergency fire mode 6 to 255 Emergency stop N B Remove emergency command clears a fault and resets the inverter 4 5 5 nviDrvReset Reset command SNVT type SNVT_state 83 It provides a reset function for the inverter or the option unit Reset is valid when the variabl...

Page 19: ...anging rotating direction However the rotating direction of the inverter performs correctly 4 6 3 nvoDrvCurnt Drive Output Current SNVT type SNVT_amp 1 It provides the inverter output current in amperes Valid range 0 0 to 3276 6 A It is overwritten 0 0A when the inverter faulted Unit 0 1 A 4 6 4 nvoDrvVolt Drive Output Voltage SNVT type SNVT_volt 44 It provides the inverter output voltage in volt ...

Page 20: ...ge Value Status Description 0 Trip release EMERG_NORMAL No Emergency mode 1 EMERG_PRESSURIZE Emergency pressurize mode 2 EMERG_DEPRESSURIZE Emergency depressurize mode 3 EMERG_PURGE Emergency purge mode 4 EMERG_SHUTDOWN Emergency shutdown mode 5 EMERG_FIRE Emergency fire mode 6 to 255 Emergency stop 4 6 10 nvoDrvAlarm Alarm SNVT type SNVT_switch 95 It provides the inverter fault Status nvoDrvAlarm...

Page 21: ... It is shown as hexadecimal value on the manual 2 parano_usl and paradat_usl is shown as most significant byte and least significant byte on the network tool 4 7 2 nvoInvP Parameter access reply It provides the inverter parameter access response This variable consists of special structure shown in below nviInvP field size Description mode_usi 1byte 1 Read 2 Write RAM 3 Write EEPROM FFh Abnormal ac...

Page 22: ... set f132 38 before the access The data value is 0001 hex The controller node sends receives the following data field Transmit nviInvP Receive nvoInvP mode_usi 2 2 parano_usl FA50h FA50h paradat_usl 0001h 0001h Example 3 Illegal access Illegal data is written to the inverter parameter f171 Base frequency voltage address 0171 The upper limit value is 330 0V 200V class In case of writing 360 0V the ...

Page 23: ...Network variable bound to the other network variable can transmit receive the data Binding can be made by network tool Network variable has a direction Input Output and individual type SNVT_type Binding to the same direction variable or the different type is prohibited Building Management system LIU005Z Bind Example connection nvoDrvSpeed SNVT_lev_percent Fan Coil Unit Controller nviDrvSpeed SNVT_...

Page 24: ...eive Heartbeat time nciRcvHrtBt nviDrvSpeedStpt nviDrvSpeedScale nviInvOutFreq In this case the inverter controls to stop the motor 2 Node health transmission function nciSndHrtBt nciMinOutTm This option unit informs the network manager to its own health Network variables controlled by this function are shown in the table below Variable name nciSndHrtBt nciMinOutTm nvoStatus nvoDrvSpeed v v nvoDrv...

Page 25: ...l cable length 500m or less Bus topology both terminated Total cable length 1400m or less Stub length 3m or less When recommended cable is used Level 4 22AWG Number of Network variables Input network variables 7 Output network variables 12 Configuration properties 12 Number of connected nodes 64 nodes at maximum segment However a host and a router are counted as one node Service pin function Mecha...

Reviews: