E6581467
4.2. Network variables list
Below table shows all network variables on LIU005Z.
Index
variable name
SNVT type
Unit
Default value
0
nviRequest SNVT_obj_request
--------
--------
1
nvoStatus SNVT_obj_status
--------
--------
2
nciLocation SNVT_str_asc Ascii Null
3
nciPwUpOutTm SNVT_time_sec 0.1s
0.0s
4
nciRcvHrtBt SNVT_time_sec 0.1s
0.0s
5
nciSndHrtBt SNVT_time_sec 0.1s
0.0s
6
nciMinOutTm SNVT_time_sec 0.1s 0.5s
7
nciMaxSpeed SNVT_lev_percent 0.005%
100.000%
8
nciMinSpeed SNVT_lev_percent 0.005%
0.000%
9
nciNmlSpeed SNVT_rpm
1min
-1
1800min
-1
10
nciNmlFreq SNVT_freq_hz
0.1Hz
60.0Hz
11
nciRampUpTm SNVT_time_sec 0.1s
10.0s
12
nciRampDownTm SNVT_time_sec
0.1s
10.0s
13
nciDrvSpeedScale SNVT_lev_percent 0.005%
100.000%
14
nviDrvSpeedStpt SNVT_switch
0.5%,1 {0.0%,
-1}
15
nviDrvSpeedScale SNVT_lev_percent 0.005%
nciDrvSpeedScale
16
nviInvSetFreq SNVT_freq_hz 0.1Hz
3276.7Hz
(Invalid)
17
nviEmergOverride SNVT_hvac_emerg binary
EMERG_NORMAL
18
nviDrvReset SNVT_state boolean
--------
19
nvoDrvSpeed SNVT_lev_percent
0.005%
--------
20
nvoDrvCurnt SNVT_amp
0.1A --------
21
nvoDrvVolt SNVT_volt
0.1V
--------
22
nvoDrvPwr SNVT_power_kilo
0.1kW
--------
23
nvoDrvRunHours SNVT_time_hour
1h
--------
24
nvoInvOutFreq SNVT_freq_hz
0.1Hz --------
25
nvoDrvSpeedOtpt SNVT_switch
0.5%,1
--------
26
nviEmergStatus SNVT_hvac_emerg
binary
--------
27
nvoDrvAlarm SNVT_switch 0.5%,1 --------
28
nvoTypeVer
SNVT_str_asc Ascii
Version
29 nviInvP
specific --------
--------
30
nvoInvP specific
--------
--------
- 10 -