– 2 –
Hydro Unit
Installation Manual
EN
1
General information
System combination
General specifications
Outdoor Unit
Single Phase model
3 Phase model
Outdoor Unit
Hydro Unit
HWS-
455H-E
HWS-
805H-E
HWS-
1105H-E
HWS-
1405H-E
HWS-
1105H8-E
HWS-
1405H8-E
HWS-
1605H8-E
HWS-
1105H8R-E
HWS-
1405H8R-E
HWS-
1605H8R-E
Backup
heater
HWS-455XWHM3-E
–
–
–
–
–
–
–
–
–
~, 3 kW
HWS-805XWHM3-E
–
–
–
–
–
–
–
–
–
~, 3 kW
HWS-805XWHT6-E
–
–
–
–
–
–
–
–
–
3N ~, 6 kW
HWS-805XWHT9-E
–
–
–
–
–
–
–
–
3N~, 9 kW
HWS-1405XWHM3-E
–
–
~, 3 kW
HWS-1405XWHT6-E
–
–
3N~, 6 kW
HWS-1405XWHT9-E
–
–
3N~, 9 kW
220-230 V model
3 phase model
3 phase with Cord Heater
Outdoor unit
HWS-455H-E
HWS-805H-E
HWS-1105H-E
HWS-1405H-E
Power supply
220-230 V ~ 50 Hz
Type
INVERTER
Function
Heating & Cooling
Heating
Capacity
(kW)
4.5
8.0
11.2
14.0
Input
(kW)
0.92
1.79
2.30
3.11
COP
(W/W)
4.90
4.46
4.88
4.50
Cooling
Capacity
(kW)
4.5
6.0
10.0
11.0
Input
(kW)
1.46
1.94
3.26
3.81
EER
(W/W)
3.08
3.10
3.07
2.89
Refrigerant
R410A
Dimension
HxWxD
(mm)
630x800x300
890x900x320
1,340x900x320
Outdoor unit
with Cord heater
HWS-
1105H8-E
HWS-
1405H8-E
HWS-
1605H8-E
HWS-
1105H8R-E
HWS-
1405H8R-E
HWS-
1605H8R-E
Power supply
380-400 V 3N~ 50 Hz
Type
INVERTER
Function
Heating & Cooling
Heating
Capacity
(kW)
11.2
14.0
16.0
11.2
14.0
16.0
Input
(kW)
2.34
3.16
3.72
2.34
3.16
3.72
COP
4.80
4.44
4.30
4.80
4.44
4.30
Cooling
Capacity
(kW)
10.0
11.0
13.0
10.0
11.0
13.0
Input
(kW)
3.26
3.81
4.80
3.26
3.81
4.80
EER
3.07
2.89
2.71
3.07
2.89
2.71
Refrigerant
R410A
Dimension
HxWxD
(mm)
1,340x900x320
Cord heater
(W)
–
75
2-EN