6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 928 -
As the threshold voltage is expressed with Table 5.4-5, the user should set
High
or
Low
to
match to the voltage value to input to binary inputs. Table 5.4-6 shows the recommended
settings.
This matter means that the user should also set a threshold voltage at the power supply unit
to determine the degree of the power failure (see
Chapter: Technical description: Power supply
module
).
Table 5.4-6 Recommended setting for the voltage level
(a) In the case of DC rated voltage “110-250 Vdc”
Voltage value
to input to binary inputs
Recommended setting for the voltage level
250V
220V
High
125V
110V
Low
(b) In the case of DC rated voltage “24-60 Vdc”
Voltage value
to input to binary inputs
Recommended setting for the voltage level
60V
48V
High
30V
24V
Low