6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)
- 927 -
(i)
Setting threshold level
For Standard type (the BI1A module and others)
The voltage level "High or Low", which tells a threshold of pick up / drop off, is selectable using
the selection switch
[THRES_Lvl]
.
Table 5.4-5 shows the threshold voltage of picking-up/dropping-off for binary inputs at the high
and low level. This also shows how to set them with the selection switch.
Table 5.4-5 Threshold voltage of picking-up / dropping-off for binary inputs
(a) In the case of DC rated voltage “110-250 Vdc”
Voltage level
Threshold voltage of picking-up / dropping-off for binary inputs
How to set
Note
High
Typical 136V
Selection switch
[THRES_Lvl] = High
—
Low
Typical 71V
Selection switch
[THRES_Lvl] = Low
This is default.
(b) In the case of DC rated voltage “24-60 Vdc”
Voltage level
Threshold voltage of picking-up / dropping-off for binary inputs
How to set
Note
High
Typical 30V
Selection switch
[THRES_Lvl] = High
—
Low
Typical 15V
Selection switch
[THRES_Lvl] = Low
This is default.
Summary of Contents for GR 200 Series
Page 1047: ...6F2S1915 0 46 GRZ200 Soft 031 032 1026 Figure 8 3 4 Screen shot from GR TIEMS ...
Page 1354: ...6F2S1915 0 46 GRZ200 Soft 031 032 1333 Appendix 1 Signal list for common function ...
Page 1410: ...6F2S1915 0 46 GRZ200 Soft 031 032 1389 This page is intentionally blank ...
Page 1480: ...6F2S1915 0 46 GRZ200 Soft 031 032 1459 Appendix 6 Ordering ...
Page 1497: ...6F2S1915 0 46 GRZ200 Soft 031 032 1476 Appendix 7 Technical data ...
Page 1518: ...6F2S1915 0 46 GRZ200 Soft 031 032 1497 Appendix 8 Manufacture setting ...
Page 1523: ...6F2S1915 0 46 GRZ200 Soft 031 032 1502 Appendix 10 CT requirement ...
Page 1531: ...6F2S1915 0 46 GRZ200 Soft 031 032 1510 Appendix 12 Engineering exercise ...
Page 1563: ......