– 145 –
8. OUTDOOR UNIT INSTALLATION MANUAL
Engineering Data book
2. Serial installation of two or more units
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of
the unit should be lower than the height of the outdoor
unit.
Standard installation
Installation of Outdoor Unit
• Before installation, check the strength and
horizontalness of the base so that abnormal sounds
do not emanate.
• According to the following base diagram, fix the base
firmly with the anchor bolts.
• (Anchor bolt, nut: M10 x 4 pairs)
• As shown in the figure below, install the foundation
and vibration-proof rubber pads to directly support
the bottom surface of the fixing leg that is in contact
with and underneath the bottom plate of the outdoor
unit.
* When installing the foundation for an outdoor unit
with downward piping, consider the piping work.
Set the out margin of the anchor bolt to 15 mm or less.
• When water is to be drained through the drain hose,
attach the following drain nipple and waterproof
rubber cap, and use the drain hose (Inner diam:
16 mm) sold on the market. Also seal knockout hole
and the screws securely with silicone material, etc.,
to prevent water from leaking.
Some conditions may cause dewing or dripping of
water.
200
or
mo
re
1,
00
0 or
mor
e
300 or
more
300 or
more
1,000 or
more
300 or
more
1,500 or
more
2,000 or
more
200 or
more
150
150
600
525
45
365
400
Drain nipple
mounting hole
Drain hole
Drain hole
GOOD
Fixing leg
Absorb vibration
with vibration-proof
rubber pads
Foundation
GOOD
Bottom plate of
outdoor unit
Foundation
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.
NO GOOD
If only the end of the
fixing leg is supported, it
may deform.
Do not support the
outdoor unit only with
the fixing leg.
Foundation
15 or less
Summary of Contents for ESTIA HWS-1501CSHM3-E
Page 3: ...2 1 INTRODUCTION ...
Page 7: ...6 2 SYSTEM OVERVIEW ...
Page 11: ...10 3 SYSTEM SPECIFICATION ...
Page 60: ...59 5 OUTDOOR UNIT ...
Page 79: ...78 6 HOT WATER CYLINDER ...
Page 85: ...84 7 HYDRO UNIT INSTALLATION MANUAL ...
Page 132: ... 131 7 HYDRO UNIT INSTALLATION MANUAL Engineering Data Book MEMO ...
Page 133: ...132 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Page 162: ... 161 8 OUTDOOR UNIT INSTALLATION MANUAL Engineering Data book MEMO ...
Page 163: ...162 9 OWNER S MANUAL ...
Page 179: ...Air to Water Heat Pump Engineering Data Book Oct 2010 ...