3.2 Network Parameter Setting
3
3.2 Network Parameter Setting
Set network parameters using the operation mode setting switches and host ID setting
switches.
For the switch setting procedures, refer to Table 3-1, Table 3-2 , Table 3-3 , and Table 3-
4.
Set the following network parameters on the EN6 module.
• IP address type
• Host ID
• Multicast address group
Be sure to set an IP address type and a host ID. Set a multicast address group in case of
using multicast transmission.
There are two IP address types, Class B (general) and CIEMAC 1200, in the EN6
module, but an arbitrary type can also be set using the Engineering Tool.
If controllers are dualized, register both parameters of primary and secondary controller
from configuration editor of engineering tool. Selection of primary and secondary is
performed on "comm. partner" of parameter setting window. (Refer to 3.2.4 Setting with
Engineering tool (4).)