![Toshiba EB621 Operation Manual Download Page 29](http://html.mh-extra.com/html/toshiba/eb621/eb621_operation-manual_424802029.webp)
6F8C0879
17
3.1 Switch Setting
3
There are two 4-bit DIP switches in the front and side panel of EN651 and EN661. Each
of switches for EN651 and EN661 is described in Table 3-3
Note:
This mode is valid for EN651 only. (Not applicable to EN661 dual systems. If this
mode is used, it is valid for line A only, provided that a single socket interface is
employed.)
Table 3-3 Operation Mode Setting Table (EN651, EN661)
Switch No. Name
Function
Setting
Default
(Before
shipment)
Front
Panel
1
DL
Download
on:Download
off
2
IPF
IP address restriction
(Note)
on : Free, off : Restricted
off
3
IP0
IP address type
IP1
IP0
Operation
IP1=off
IP0=off
(Class B
setting)
off
off
Class B (General)
off
on
Reserve
4
IP1
on
off
TOSDIC-CIE 1200
on
on
Set from tool
Side
Panel
1
M0
Operation mode
M1
M0
Operation
M1=off
M0=off
(Normal setting)
off
off
Normal
off
on
Reserve
2
M1
on
off
Reserve
on
on
Memory clearance
3
SEL
Spare 0
Reserve
4
GW
Relay function (future)
on : Provided, off : None
Table 3-4 Operation Mode Setting Table (EN651A)
Switch No. Name
Function
Setting
Default
(Before
shipment)
1
M0
Operation mode
M1
M0
Operation
M1=off
M0=off
(Normal setting)
off
off
Normal
off
on
Download
2
M1
on
off
Test program
on
on
Reserve
3
SL
Debug
on : WDT invalid, off : WDT valid
off
4
GW
Relay function (future)
on : Provided, off : None
off
5
S0
Spare 0
Unused
off
6
IPF
IP address restriction
on : Free, off : Restricted
off
7
IP0
IP address type
IP1
IP0
Operation
IP1=off
IP0=off
(Class B
setting)
off
off
Class B (General)
off
on
Reserve
8
IP1
on
off
TOSDIC-CIE 1200
on
on
Set from tool