E6581737
- 8 -
2.4. VF-MB1/S15 Communications-related parameters
In a network, VF-MB1/S15 (DEV003Z) serves as a DeviceNet slave device. DEV003Z
configuration is set by the following parameters.
Parameter
Function
Adjustment range
Default setting
c200
DEV003Z
MAC ID
0 to 63
63
c201
DEV003Z
Communication
baud rate
DEV003Z communication baud rate is set.
0: AUTO *
1: 125kbps
2: 250kbps
3: 500kbps
0
c202
DeviceNet
Baud rate monitor
DeviceNet communication baud rate is shown.
1: 125kbps
2: 250kbps
3: 500kbps
-
c203
DEV003Z
Assembly Object
0: Instance 20/70
1: Instance 21/71
2: Instance 100/150
3: Instance 101/151
4: Instance 102/152
5: Instance 105/155
0
c100
Communication error
detection delay time
0.0 to 100.0s
0.0
c101
Inverter operation at the
communications
loss action
(Network wire breaks)
0: Stop and Communication release **
(follows
cmod
and
fmod
setting)
1: None
2: Deceleration stop
3: Coast stop
4: Emergency stop
(
err8
) ***
5: Preset speed operation command
(Operating at the preset speed operation
frequency set with
c102
)
4
c102
Preset speed
operation selection
0: None
1 to 15:Preset speed
(
sr1
-
sr7
,
f287
-
f295
)
0
c103
Communication
time-out condition
selection
0: Disconnection detection
1: When communication mode enable (Both
cmod
and
fmod
are set CANopen or COM
option)
2: 1+Driving operation
0
f899
Network option
reset setting
0: None
1: Resetting the DEV003Z and the inverter
0
fd67
DEV003Z versioon
DEV003Z firmware version
(ex. 0x1101 means "V1.01")
-
*
DeviceNet baud rate is 500kbps and with a few slaves in the network, auto baud rate function might not
work.
**
Do not set at VF-MB1
V1.00
.
*** When the parameter is changed, the power must be cycled (or set
f899
to
1
) to the VF-MB1/S15 for the
changes to take effect.
1
to
f899
by the DeviceNet communication might not be able to be set.
Please note that inverter keeps driving when the communication is lost if
1
(None) is set to the
parameter
c101
(Inverter operation at the communications loss action).
Caution