E6581737
- 28 -
3.4.6.2.
fa23
(Communication command 2)
bit
Function
0
1
Note
0
(Reserved)
-
-
-
1
Electric power quantity
reset
OFF
Reset
Electric power quantity (
fe76
,
fe77
) reset
2
(Reserved)
-
-
-
3
(Reserved)
-
-
-
4
(Reserved)
-
-
-
5
(Reserved)
-
-
-
6
(Reserved)
-
-
-
7
Maximum deceleration
forced stop
Normal
Enabled
-
8
Acceleration/decele-
ration selection 1
9
Acceleration/decele-
ration selection 2
00: Acceleration/deceleration 1
01: Acceleration/deceleration 2
10: Acceleration/deceleration 3
Select
acceleration/deceleration
1-4 by combination of two bits..
AD1:
acc
,
dec
AD2:
f500
,
f501
AD3:
f510
,
f511
10 (Reserved)
-
-
-
11 (Reserved)
-
-
-
12 OC stall level switch
OC stall 1
OC stall 2
OC stall 1:
f601
OC stall 2:
f185
13 (Reserved)
-
-
-
14 (Reserved)
-
-
-
15 (Reserved)
-
-
-
Note: Set 0 to reserved bit.
3.4.6.3.
fa07
(frequency reference from internal option)
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,
80 / 0.01 = 8000 = 0x1F40 (Hex.)
3.4.6.4.
fa50
(Terminal output data from communication)
By setting up the data of the bit 0 - 1 of terminal output data (
fa50
) from communication, setting data (OFF or
ON) can be outputted to the output terminal.
Please select the functional number 92 - 95 as the selection (
f130
-
f138
) of the output terminal function
before using it.
bit
Output TB function name
0
1
0
Specified data output
1
(Output terminal No.: 92, 93)
OFF
ON
1
Specified data
output 2
(Output terminal No.: 94, 95)
OFF
ON
2-15
(Reserved)
-
-
Note: Set 0 to reserved bit
3.4.6.5.
fa51
(Analog output (FM) data from communication)
Use this function, set the FM terminal meter selection parameter (
fmsl
) to 18 (communication data output).
This makes it possible to send out the data specified as FM analog output data (
fa51
) though the FM analog
output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the VF-MB1/S15 instruction manual for details.