4. DeviceNet Local/Remote Operation
The example below shows how to configure the VF-MB1/S15 for local / remote operation.
<Terminal function>
F terminal ............ RUN command
R terminal............ DeviceNet /Local (Terminal in this example) switching
VIB terminal......... Operation frequency command
<Wiring>
<Parameter setting>
cmod
(command mode selection) = 0 (terminal board)
fmod
(frequency setting mode selection 1) = 2 (VIB)
f112
(input terminal selection 2 (R)) = 48 (DeviceNet/Local control)
<Operation>
R-CC terminal open:
VF-MB1 is controlled as slave device of DeviceNet.
R-CC terminal closed:
F-CC terminal short to RUN
F-CC terminal open to STOP
Output frequency is set up by the VIB signal input.
5. EDS file
Even if access to each parameter of VF-MB1 or VF-S15 uses a configuration tool and an EDS
file, it is possible. As for acquisition of an EDS file, please contact your Toshiba distributor.
Please use what was in agreement with the software version of usage's VF-MB1 or VF-S15.
- 44E -
VF-MB1/S15
F
R
P24
PP
VIB
Variable resistor for adjustment
10k ohm
DeviceNet /Local
Switch
Operation command
SW1
SOURCE
CC
OUT
SINK