LQ500  

EJL-106J 

 

Converter Specifications 

Output signals 

• Density (consistency) measurement output:  

4-20mAdc (load resistance 750 ohm maximum, 

isolated output.) 

• Density (%TS, consistency) fault or 

Maintenance signal:  

125Vac, 0.1A (resistive load) solid state contact; 
opens when an error occurs in the converter or 
when the LQ500 is in the setting change mode, 
otherwise the contact remains closed. 

• Communication signal:  

Digital signal is superimposed on 4-20mAdc 

current signal (conforming to HART protocol (*1)). 

Load resistance: 240 to 750 ohm 

Load capacity: 0.25

µ

F maximum 

*1 HART (Highway Addressable Remote Transducer) 

protocol is a communications protocol for industrial 
sensors recommended by HCF (HART 
Communication Foundation). 

Note: The optional BF100 configurator can be used to 

operate the LQ500 from remote places by 
connecting the communication cable between the 
LQ500’s 4-20 mA dc output signal lines. 

Input signals 

• External synchronized input signal: 

In order to avoid problems of density (%TS, 
consistency) measurement such as 
inhomogeneous condition caused by 
discontinuous process operation and empty pipe 
condition caused by stopping process operation. 

<Specification> 

One dry “make” contact;  

Contact capacity of approximately 5Vdc. 0.1A is 
required. This contact signal can be used to start 
or stop density (consistency) measurement in 
synchronization with an external contact, such as 
the contacts on a pump. 

The measurement starts or stops as follows: 

Contact closed: Starts density (%TS, 

consistency) measurement. 

Contact open: Stops density (%TS, consistency) 

measurement. 

• Density multiplier switching signal: 

In order to achieve selecting up to 4 kinds of 
liquid concentration measurement independently 
as maximum. 

<Specification> 

Two voltage signals described below are required: 

Input voltage: H level:  20 to 30 Vdc 

L level:  2 Vdc or less 

Input resistance: Approx. 3k ohm 

• Internal conductivity correction function: 

      This function reduces the influence (density 

variation) of the conductivity changing by using 
the measured valve of LQ500. Thus, this function 
does not need to input the conductivity meter 
signal (the correction factor of this function is 
calibrated with sodium chloride).  If this function 
(Internal conductivity correction) does not reduce 
the density variation by the conductivity changing, 
you can use “External Conductivity correction”. 

• External conductivity correction function: 

Conductivity correction signal: 

Needs to prepare an additional conductivity meter 
when using this function. Install in where is able 
to have a stable and accurate measurement. 

<Specification> 

Input signal: 4 to 20mAdc 

Conductivity range: 0 to 10mS/cm 

Update period for density (%TS, consistency) 
measurement output and display: 
Approx. 1 second 

Functions by software as standard: 

• Data saving function: 

In order to save measurement data into the 
memory of converter temporary.  
The oldest data is overwritten. 

<Specification> 

Data storage points: 256 points maximum. 

Period: 1 to 1,800 minutes (1 minute each).  

ex 1: The data is saved for approx. latest 4.26 

hours when programming every minute. 

ex 2: The data is saved for approx. latest 21.3 

hours when programming every 5 minutes. 

 

 

 

 

Summary of Contents for Density (Consistency) Meter LQ500

Page 1: ...ollowing cases Possibility of unfilled condition a When it is installed at the discharge of a pump b When installation is horizontal and unfilled condition occurs inside the pipe c A process where the pipe becomes unfilled when the operation is stopped Cable for power supply Detector converter Ground resistance 100 ohm or less Density consistency measurement output 4 20mA Cable for communication D...

Page 2: ... reagent Electric resolution Meter size 50 mm 2 80 mm 3 to 300 mm 12 Electric resolution 0 002 TS 0 001 TS Note 1 Above values are the results of computing ability in the phase measurements of the converter Note 2 Density TS consistency determination resolution for sample reagent Meter size 50 mm 2 80 mm 3 to 300 mm 12 Density TS consistency determination repeatability 0 1 TS 0 05 TS The density T...

Page 3: ...ximum working pressure ANSI Class 150 1 MPa 150 psi DIN10 and BS10 1 MPa 10 bar DIN 16 1 6 MPa 16 bar JIS 10K 1 MPa 10 kgf cm2 Note Each product was passed a hydraulic test under twice pressure rate for 15 minutes toward the specification Fluid temperature 0 to 100 deg C 32 to 212 deg F without freezing and bubbles conditions Allowable fluid conductivity Meter size Fluid conductivity 50 mm 2 20 mS...

Page 4: ...itable for your CIP or not before cleaning 2 The smoothness inside the pipe on this material is Type Meter size Smoothness Standard type 50 to 200 mm 2 to 8 No buffing 250 300 mm 10 12 Buffing 150 Option type 50 to 300 mm 2 to 12 Buffing 150 3 State the wetted materials when you choose these options 4 The materials of them are changed for abrasive applications Need to choose the specification code...

Page 5: ...density TS consistency measurement Contact open Stops density TS consistency measurement Density multiplier switching signal In order to achieve selecting up to 4 kinds of liquid concentration measurement independently as maximum Specification Two voltage signals described below are required Input voltage H level 20 to 30 Vdc L level 2 Vdc or less Input resistance Approx 3k ohm Internal conductivi...

Page 6: ...ation N when the external synchronized operation starts LQ500 measure the phase of microwave and calculate the density TS from the phase changes Because the phase is limited from 0 degree to 360 degrees LQ500 use the rotation N when the phase is over 360degree But the range of density is wide over the 360 degree LQ500 may not know the number of the rotation N when the pump starts If the density is...

Page 7: ...x 44 97 lb Approx 42 200 8 320 12 6 290 11 4 300 11 8 Approx 50 Approx 52 Approx 54 119 lb Approx 48 250 10 300 11 8 315 12 4 350 13 8 Approx 65 Approx 68 Approx 68 150 lb Approx 64 300 12 360 14 2 340 13 4 350 13 8 Approx 78 Approx 85 Approx 99 218 lb Approx 76 110 4 3 119 4 7 Detector Converter communication cable port Steel pipe 50A 2 360 14 2 390 15 4 234 9 2 Density signal output port Contact...

Page 8: ...t measure accurately The range of measurable density less than 1 second c 1 000 Meter Size 50 80 100 150 200 250 300 Density TS 16 8 10 5 8 4 5 6 4 2 3 4 2 8 500 19 7 600 23 6 Maintenance space Back Front Detector Converter RF part A 500 mm 19 7 maintenance space is also needed above unit 500 19 7 600 23 6 600 23 6 500 19 7 Maintenance space Unit mm inch Figure 5 Clearance space Piping Precautions...

Page 9: ...d radio waves will leak out However the amount is about equal to PHS and one tenth of mobile phones 16 For both horizontal and vertical piping systems install a support stand under the density meter with bolts put through the installation holes M8 size on the bottom of the density meter Then install the support stand together with the density meter to a solid ground or wall Bolts four M8 bolts are...

Page 10: ... Screws at the terminals are needed to tighten with 1 2 N m torque 1 4 N m is maximum 10 Do not turn on the power supply under the uninstalled condition 11 Each cable in the communication cable and power supply cable between detector and converter has banded marks for each terminal Connect them correctly without any mismatches L1 L2 Tx TX Rx Rx SG FG 24V 0V FG Ec Ec FG Tx Tx Rx Rx SG FG 24V 0V FG ...

Page 11: ...nction is used By connecting the cable lead of the optional BF100 configurator to the density TS consistency measurement output you can operate the LQ500 from remote places 1 Make sure the load resistance of 4 20mAdc line of output is between 240 and 750 ohm and the load capacitance is 0 25µF maximum 2 The BF100 s cable lead can be connected to the LQ500 anywhere along the current output line For ...

Page 12: ...pe for abrasive application Note 2 Cable length between detector RF part converter A 10 m 32 8 ft standard B 20 m 65 6 ft C 30 m 98 4 ft D 40 m 131 2 ft E 50 m 164 ft X None Note 2 Note 1 The differences between standard type are RTD sensor and Applicator window Note 2 Toshiba recommends to using our specified cable Table 5 Type Specification Code BF100 Hand held Terminal Model Specification Code ...

Reviews: