LQ500
2
Specifications
■
Overall Specifications
Measurement method:
Microwave phase difference method
Measurement range:
Meter size
50 mm (2”)
80 to 300 mm
(3” to 12”)
Span (*2)
2 to 50 %TS (*1) 1 to 50%TS (*1)
Lower limit setting
range (4 mA)
0 to 48%TS
0 to 49%TS
Upper limit setting
range (20 mA)
2 to 50%TS
1 to 50%TS
Setting increments
0.1%TS
*1 TS: Total Solids
*2 Span = Upper range – Lower range
*3 The material to be measured must be fluid and be filled
evenly with no voids.
*4 If the density changes rapidly (less than 1second),
the LQ500 may not measure accurately. The range
of measurable density (less than 1 second)
(c = 1.000)
Meter Size
50
80
100
150
200
250
300
Density [% TS]
16.8 10.5
8.4
5.6
4.2
3.4
2.8
Repeatability:
Meter size
50 mm (2”)
80 to 300 mm
(3” to 12”)
Repeatability
±0.02%TS
±0.01%TS
Note 1: Above values are the results of computing ability in the
phase measurements of the converter.
Note 2: Density (%TS, consistency) determination
repeatability for sample reagent;
Meter size
50 mm
(2”)
80 to 300 mm
(3” to 12”)
Density
(consistency)
determination
repeatability
For the full scale
value of 2%TS
or greater
±2%FS
±2%FS
For the full scale
value of less
than 2%TS
±4%FS
*The characteristics of sample reagent has errors due to
sample tests such as uneven density (%TS, consistency)
distribution.
*Full scale is the maximum value in the measurement range,
which is the upper limit setting range.
Linearity:
Meter size
50 mm (2”)
80 mm (3”)to
300 mm (12”)
Full-scale 2%TS or more
±2%TS
±2%TS
Less than full-scale 2%TS
±4%TS
Note: The values are taken at measuring points above 5% of
full-scale using simulated reagent.
Electric resolution:
Meter size
50 mm (2”)
80 mm (3”)to
300 mm (12”)
Electric resolution
0.002%TS
0.001%TS
Note 1: Above values are the results of computing ability in
the phase measurements of the converter.
Note 2: Density (%TS, consistency) determination
resolution for sample reagent;
Meter size
50 mm
(2”)
80 mm (3”)to
300 mm (12”)
Density(%TS, consistency)
determination repeatability
0.1%TS
0.05%TS
* The density (%TS, consistency) determination resolution
stated above is defined due to manufacturing limitation to
make reagents with stable distribution and a minimum
difference of fluid density (consistency).
<Notice>
1. Install a sample tap near the LQ500 as close as
possible to get an accurate density (%TS,
consistency) measurement using the LQ500.
2. Take several samples in rapid sequence for
more accurate density (%TS, consistency)
measurement with less human error factors.
Environmental conditions:
Items
Temperature range
Humidity range
Detector
Standard: 0 to 50 deg.C
(32 to 122 deg.F)
5 to 90%RH
(no condensation)
Converter
0 to 50 deg.C
( 32 to 122 deg.F)
Temperature code: T4A
Structure: Converter: IP65,
Detector: IP67, Watertight
Note: Outdoor installation is possible. However, provide
a sunshade for the converter section if direct
sunlight is unavoidable.
Microwave power: Approx. 10 mW
Vibration resistance:
No resonance to the following levels of vibration:
(1) No failure for 5 to 150 Hz with the following
acceleration in each device for 30 minutes in each
axis of X, Y, and Z (90 minutes);
Converter: 4.9 m/s
2
, Detector: 25m/s
2
(2) No failure for 5 to 150Hz with the following
acceleration in each device for 3 minutes in each
axis of X, Y, and Z, 10 times (90 minutes as total);
Converter: 4.9 m/s
2
, Detector: 25m/s
2
Note: Avoid using the LQ500 in an environment with
constant vibration.