5.2 Controller Interface
Unified Controller nv series type1 light Communication Interface Module (CF622) Instruction Manual
47
■
Receive Processing Operation
--- Normal mode (operation mode mode3)
Trans data
(3)
RX_RDY
(6)
(1)
RX_CMP
RX_ERR
CF622 Control
User's application
(4)
MREAD instruction
RX_ST
(2)
(5)
Receive data
Receive data
Figure 5-20 Receive processing operation (mode 3)
(1) When CF622 receives data, RX_CMP is set to 1.
(2) Set RX_ST to 1 from user’s application.
(3) RX_CMP is reset to 0, RX_RDY is set to 1.
(4) Read received data from receive data area using MREAD instruction.
(5) Reset RX_ST to 0 from user’s application.
(6) RX_RDY is reset to 0.