– 73 –
8-2-5. Outdoor Unit
Red
White
Black
Red
White
Black
Red
White
Black
No.
1
2
3
Part name
Compressor
(Model :DA111A1FD-21F)
Compressor
(Model :DA220A2-22L)
Compressor
(Model :DA422A3F-25M)
Checking procedure
Measure the resistance value of each winding by using the tester.
Measure the resistance value of each winding by using the tester.
Measure the resistance value of each winding by using the tester.
Revised : Feb. 2010
Position
Red – White
White – Black
Black – Red
Resistance value
1.07
Ω
Under 20°C
Position
Red – White
White – Black
Black – Red
Resistance value
0.606
Ω
Under 20°C
Position
Red – White
White – Black
Black – Red
Resistance value
0.264
Ω
Under 20°C