– 43 –
4) The time of above d can be changed by
exchanging jumper [J805] and [J806] of the
outdoor control P.C. board.
(Setting at shipment: 150 minutes)
A zone
B zone
C zone
D zone
In normal To
In abnormal To
When status (TE0 – TE) – (To0 – To)
≥
37.4°F (3°C)
When status (TE0 – TE)
≥
37.4°F (3°C)
continued for 20 seconds
continued for 20 seconds
When status (TE0 – TE) – (To0 – To)
≥
35.6°F (2°C)
When status (TE0 – TE)
≥
35.6°F (2°C)
continued for 20 seconds
continued for 20 seconds
When status (TE
≤
–9.4°F (–23°C)) continued for 20 seconds
When compressor operation status of TE < 28.4°F (–2°C) is calculated by d portion
{
: Short circuit,
×
: Open
10. Defrost control
1) In heating operation, defrost operation is performed when TE sensor satisfies any condition in A zone to
D zone.
2) During defrosting operation, it finishes if TE sensor continued 53.6°F (12°C) or higher for 3 seconds or
continued 44.6°F (7°C)
≤
TE < 53.6°F (12°C) for 1 minute.
The defrost operation also finishes when it continued for 10 minutes even if TE sensor temperature was
44.6°F (7°C) or lower.
3) After defrost operation was reset, the compressor stopped for approx. 40 seconds and then the heating
operation starts.
∗
The minimum TE value and To value between 10 and 15 minutes after heating operation has started
are stored in memory as TE0 and To0, respectively.
0
10
15
39
45
55
d
[min.]
∗
TE ˚F (˚C)
28.4 (–2)
23.0 (–5)
14.0 (–10)
–9.4 (–23)
A zone
A zone
B zone
B zone
C zone
C zone
D zone
D zone
A zone
B zone
C zone
D zone
Start of heating operation
J805
{
{
×
×
d
150 minutes
Setting at shipment
90 minutes
60 minutes
30 minutes
J806
{
×
{
×
Summary of Contents for CARRIER RAV-SP180AT2-UL
Page 12: ... 12 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 Outdoor Unit RAV SP180AT2 UL ...
Page 13: ... 13 RAV SP240AT2 UL ...
Page 14: ... 14 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...
Page 107: ... 107 12 EXPLODED VIEWS AND PARTS LIST 12 1 Outdoor Unit 12 1 1 RAV SP180AT2 UL ...
Page 110: ... 110 12 1 2 RAV SP240AT2 UL ...
Page 113: ... 113 12 1 3 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...