– 17 –
RAV-SP240AT2-UL
Capillary
Refrigerant pipe
at liquid side Ø9.5
Packed valve
Refrigerant pipe
at gas side Ø15.9
Ball valve
Strainer
Strainer
TD
sensor
TS sensor
TO sensor
TL sensor
TE sensor
Heat exchanger
Ø8, 2 rows, 34 stages
FP1.45, flat fin
Accumulator
(1.8L)
Accumulator
Sub-ass’y
Rotary compressor
(DA220A2F-22L)
In cooling operation
In heating operation
4-way valve
(STF-0218G)
Ø25 × L180
Ø2 × Ø3 × 600L
Ø2 × Ø3 × 550L
Ø2 × Ø3 × 450L
Ø2 × Ø3
× 450L
Ø25 × L210
Muffler
Muffler
Muffler
PMV
(Pulse Motor Valve)
(CAM-B30YGTF-2)
Standard
Cooling Overload
Low load
Standard
Heating Overload
Low load
Pressure
(psi)
(MPa)
Pd
Ps
Pd
Ps
404.6 129.1 2.79 0.89
511.9 155.2 3.53 1.07
248.0 104.4 1.71 0.72
384.3 98.6 2.65 0.68
464.0 161.0
3.2
1.11
337.9 30.5 2.33 0.21
Pipe surface temperature °F (°C)
Discharge
Suction
Indoor heat Outdoor heat
exchanger
exchanger
(TD)
(TS)
(TC)
(TE)
158
.0
55.4
51.8
102.2
(70)
(13)
(11)
(39)
177.8
62.6
57.2
118.4
(81)
(17)
(14)
(48)
107.6
44.6
37.4
64.4
(42)
( 7)
( 3)
(18)
165.2
39.2
111.2
37.4
(74)
( 4)
(44)
( 3)
168.8
66.2
125.6
59
(76)
(19)
(52)
(15)
199.4
–0.4
87.8
–4
(93)
(–18)
(31)
(–20)
Compressor
drive revolution
frequency
(rps)
58.2
65
.0
30
.0
61.5
28
.0
99.6
Indoor
fan
HIGH
HIGH
LOW
HIGH
LOW
HIGH
Indoor/Outdoor
temp. conditions
(DB/WB) °F °C)
Indoor
Outdoor
80.6/66.2
95/–
(27/19)
(35/–)
89.6/75.2
109.4/–
(32/24)
(43/–)
64.4/59.9
23/–
(18/15.5)
(–5/–)
68
44.6/42.8
(20/–)
(7/6)
86/–
75.2/64.4
(30/–)
(24/18)
59/–
5/–
(15/–)
(–15/–)
Revised : Feb. 2010
Summary of Contents for CARRIER RAV-SP180AT2-UL
Page 12: ... 12 2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 Outdoor Unit RAV SP180AT2 UL ...
Page 13: ... 13 RAV SP240AT2 UL ...
Page 14: ... 14 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...
Page 107: ... 107 12 EXPLODED VIEWS AND PARTS LIST 12 1 Outdoor Unit 12 1 1 RAV SP180AT2 UL ...
Page 110: ... 110 12 1 2 RAV SP240AT2 UL ...
Page 113: ... 113 12 1 3 RAV SP300AT2 UL RAV SP360AT2 UL RAV SP420AT2 UL ...