User’s
Manual
39
5. Operation Procedure
5.2 Received message read sequence
5.2.1
Flag control timing
In case of receiving a message, the following flags are used for handshaking between
T3 and AS311. These flags are the bits of the I/O registers assigned to the AS311.
Refer to section 4.1.
Read ready
Bit 7 of XW(n) for channel 1 or XW(n+1) for channel 2
Receive complete
Bit 6 of XW(n) for channel 1 or XW(n+1) for channel 2
Receive error
Bit 5 of XW(n) for channel 1 or XW(n+1) for channel 2
Read start
Bit 7 of YW(n+2) for channel 1 or YW(n+3) for channel 2
The message receiving procedure is as follows. It is called “received message read
sequence”.
AS311 receives a message
AS311
sets
Receive complete
to ON
T3
sets
Read start
to ON
Normal receiving
Receiving error
AS311 sets the message into buffer
AS311 sets the error information into
memory (receiving data area), and
buffer memory (parameter area)
sets the received message length into
buffer memory (parameter area)
AS311
sets
Read ready
to ON, and
AS311 sets
Receive error
to ON, and
resets
Receive complete
to OFF
resets
Receive complete
to OFF
T3 reads the message form buffer
T3 reads the error information from
memory (receiving data area)
buffer memory (parameter area)
by READ instruction
by READ instruction
T3
resets
Read start
to OFF
T3 resets
Read start
to OFF
AS311
resets
Read ready
to OFF
AS311 resets
Receive error
to OFF