4. Register Configuration
The following table shows the functions of I/O registers assigned to the AS311.
XW(n)
CH1 status
XW(n+1)
CH2
status
YW(n+2)
CH1
command
YW(n+3)
CH2
command
Register
Bit
Name
Description
F Write ready
1: ready to write data (transmit) for channel 1
E Transmit complete 1: transmitting has been completed normally
D Transmit error
1: transmitting has been canceled by error
XW(n)
C - 8
−
No use (always 0)
(CH1)
7 Read ready
1: ready to read the received data
6 Receive complete 1: receiving for channel 1 has been completed
5 Receive error
1: receiving error has occurred
4 - 0
−
No use (always 0)
F Write ready
1: ready to write data (transmit) for channel 2
E Transmit complete 1: transmitting has been completed normally
D Transmit error
1: transmitting has been canceled by error
XW(n+1) C - 8
−
No use (always 0)
(CH2)
7 Read ready
1: ready to read the received data
6 Receive complete 1: receiving for channel 2 has been completed
5 Receive error
1: receiving error has occurred
4 - 0
−
No use (always 0)
F Transmit start
Set to 1 to start transmitting data from channel 1
YW(n+2) E - 8
−
No use (set to 0)
(CH1)
7 Read start
Set to 1 to start reading data for channel 1
6 - 0
−
No use (set to 0)
F Transmit start
Set to 1 to start transmitting data from channel 2
YW(n+3) E - 8
−
No use (set to 0)
(CH2)
7 Read start
Set to 1 to start reading data for channel 2
6 - 0
−
No use (set to 0)
These bits are used for handshaking between T3 and AS311. The detailed
function and timing are explained in section 5.
F E D C B A 9 8 7 6 5 4 3 2 1 0
No use
No use
No use
No use
No use
No use
No use
No use
NOTE