User’s
Manual
17
2. Specifications
2.3 Transmission specifications
Item
Channel 1
Channel 2
Interface
RS-232C or RS-422
RS-232C
Transmission mode
Full-duplex
Synchronizing
Start-stop method (asynchronous)
Transmission speed
300, 600, 1200, 2400, 4800, 9600, 19200 bps
Frame format
Start bit
Data
Parity
Stop bit
1 bit
7 or 8 bits
even / odd / none
1 or 2 bits
Transmission code
ASCII
Message length
Max. 896 bytes
Configuration
One to one (Note)
Transmission distance
Max. 15 m (RS-232C)
Max. 1 km (RS-422)
Max. 15 m
Connector
D-sub 25-pin female
D-sub 25-pin female
Note) In case of RS-422 interface, multiple devices can be connected to one AS311
if the connected RS-422 devices work as slave stations and support multi-point
connection. That is, the connected RS-422 devices must have the transmission
generators which support the passive state. Also, the RS-422 devices must
support the message format which contains the selecting address. In this case,
the number of the connected RS-422 devices is limited up to 10.
On the other hand, the AS311’s transmission generator does not support the
passive state. Therefore the AS311 must be the master station in the one-to-N
configuration.
Summary of Contents for AS311
Page 8: ...6 ASCII Interface Module AS311 ...
Page 16: ...14 ASCII Interface Module AS311 ...
Page 20: ...18 ASCII Interface Module AS311 ...
Page 21: ...User s Manual 19 Section 3 Cable Connections 3 1 RS 232C connection 3 2 RS 422 connection ...
Page 24: ...22 ASCII Interface Module AS311 ...