1. AS311 Overview
Hardware reset switch
When this switch is pressed, the AS311 will be reset. Use this switch when you
have changed the switch settings.
Channel 1 and channel 2 serial ports
Used to connect the serial transmission line (RS-232C or RS-422). D-Sub 25-pin
female connectors are provided on the AS311.
The pin assignment is as follows.
Channel 1
Channel 2
(RS-232C/RS-422)
(RS-232C)
1 FG
↔
1 FG
↔
2 TXD
→
2 TXD
→
3 RXD
←
for RS-232C
3 RXD
←
4 RTS
→
4 RTS
→
5 CTS
←
5 CTS
←
6
6 DSR
←
7 SG
↔
7 SG
↔
8
8
9 5 Vdc
→
9 5 Vdc
→
10
TXDA
→
10
11
RXDA
←
for RS-422
11
12
RTSA
→
12
13
CTSA
←
13
14
14
15
15
16
16
17
17
18
18
19
19
20
DTR
→
for RS232C
20 DTR
→
21
TXDB
→
21
22
RXDB
←
for RS-422
22
23
RTSB
→
23
24
CTSB
←
24
25
25
•
The arrow on the above figure shows the signal direction.
•
FG is connected with the T3’s frame ground internally. (both channels)
•
DTR and RTS are ON while power is on.
•
Data transmitting is available when CTS is ON. DSR has no effect for transmission.
•
Pin 9 (5 Vdc) can be used to supply 5 Vdc power. (total max. 50 mA)