71
4300 Series Installation and Operation Manual
Appendix A - Installation Planning Guide
TOSHIBA
4300 UPS
Installation Planning Guide for 30/50kVA UPS
Standard System: 208/120V Input, 208/120V Output
Rev. 0
Page 2 of 2
4300-IPG-208/120v-208/120V
1. Maximum Current required at Primary AC Input based on full load output and maximum battery
charging current.
2. Output load conductors are to be installed in separate conduit from input conductors.
3. Control wires and power wires are to be installed in separate conduits.
4. Recommended AC input and output overcurrent protection based on continuous full load current per
NEC.
5. Wiring shall comply with all applicable national and local electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122. Neutral conductors to be sized per NEC
Article 310.15.
-
Primary AC Input: 3
φ
, 4-wire + ground.
-
AC Output: 3
φ
, 4-wire + ground.
-
DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type batteries (2.0 volts / cell nominal).
8. Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 VPC.
9. DC wires should be sized to allow not more than a 2-volt drop at maximum discharge current.
10. Sizing calculations based on the following assumptions:
-
Not more than 6 current-carrying conductors installed in steel conduit in ambient temperature of
30 degrees C.
-
Temperature rating of conductors and terminals: 75 deg. C.
-
Feeder distance calculations based on NEC Chapter 9, Tables 8 and 9 data, allowing for 2% AC
voltage drop.
-
Reference: 2005 NEC Handbook. Consult latest edition of applicable national and local codes for
possible variations.
11. Ratings of wires and overcurrent devices are suggested minimums. Consult with a registered
Professional Engineer within your local area for proper size selections.