TOPVERT S1 Series
E-
16
30: Over-torque 2 (ot2)
◎
31: OH2 pre–warning indication
◎
32: Motor selection output (Pr5-49)
◎
33~47: (Factory Reserved)
48: Master speed executing
49: PLC Run step 1 executing
50: PLC Run step 2 executing
51: PLC Run step 3 executing
52: PLC Run step 4 executing
53: PLC Run step 5 executing
54: PLC Run step 6 executing
55: PLC Run step 7 executing
56: PLC Run step 8 executing
57: PLC Run step 9 executing
58: PLC Run step 10 executing
59: PLC Run step 11 executing
60: PLC Run step 12 executing
61: PLC Run step 13 executing
62: PLC Run step 14 executing
63: PLC Run step 15 executing
64~79: (Factory Reserved)
◎
Pr2-26 (Factory
Reserved)
◎
Pr2-27
(Factory Reserved)
◎
Pr2-28
(Factory Reserved)
(Factory Reserved)
0
Group 3: Analog Input/Output parameters
Parame
ters
Functions Settings
Factory
Setting
User
0: Enable addition function
Pr3-00
Addition Function of the Analog
Inputs
1: Disable addition function
0
Pr3-01 Analog input noise filter time
0.00~2.00 sec
0.10
0: No functions
1: Frequency command
2: To adjust 1
st
Acceleration/deceleration time)
(same as Pr1-11, Pr1-12)
3: Over Current stall prevention level during
constant speed run on the constant torque
region (same as Pr5-12)
4: Over Current stall prevention level during accel
on the constant torque region (same as Pr5-10)
5: Over-Torque detection level 1 (ot1)
(same as Pr5-16)
6: Motor 1 Torque boost level (same as Pr5-01)
7: Auxiliary command when main frequency
command is AVI only
8: Auxiliary command when main frequency
command is ACI only
9: (Factory Reserved)
10: Auxiliary command of master frequency
command
11: PID feedback signal
12: PID offset signal (same as Pr7-05)
13: DC Braking current level (same as Pr6-00)
14: Voltage adjusts during run. (AVI Pr3-02 only)
Pr3-02
Valid
for
ACI
(Pr3-0
6)
AVI Analog Input
15: External temperatures signal
1