TOPVERT S1 Series
E-
20
Pr5-11
Over- Current Stall Prevention
low-limit level during accel on the
constant power region
Amp (0~250% of drive’s rated current)
A(120%)
Pr5-12
Over-Current Stall Prevention level
during constantant speed on the
constant torque region Operation
Amp (10~250% of drive’s rated current)
A(170%)
Pr5-13
Over- Current Stall Prevention
low-limit level during constant speed
run on the constant power region
Amp (0~250% of drive’s rated current)
A(120%)
Pr5-14
Over-Current Deceleration Time
during Operation
0.050~600.00 Sec
3.00
0
:
Disabled
1
:
Over-torque detection during constant
speed operation, stop operation after
detection.
2
:
Over-torque detection during constant
speed operation, continue to operate
after detection.
3
:
Over-torque detection during
operation, stop operation after
detection
Pr5-15
Over-Torque Detection Selection 1
(ot1)
4
:
Over-torque detection during
operation, continue operation after
detection.
0
Pr5-16
Over-Torque Detection Level 1 (ot1)
Amp(10
〜
250% of drive’s rated current)
A(150%)
Pr5-17
Over-Torque Detection Time 1 (ot1)
0.0
〜
60.0 Sec
0.1
0
:
Electronic thermal relay function
disabled
1
:
Inverter duty motor
(with independent cooling fan)
Pr 5-18
Motor 1- Electronic Thermal Relay
Selection (oL1)
2
:
Standard motor (with shaft mounted
cooling fan)
0
Pr5-19
Motor 1- Electronic Thermal Relay
Characteristic
30
〜
600 Sec
60
Pr5-20
IGBT Over-Heat pre–warning setting
(oH2)
0.0~110.0 85.0
0: Disabled
1: Over-torque detection during constant
speed operation, stop operation after
detection.
2: Over-torque detection during constant
speed operation, continue to operate
after detection.
3: Over-torque detection during entire
(acceleration, steady state,
deceleration) operation, stop operation
after detection
Pr5-21
Over-Torque Detection Selection 2
(ot2)
4: Over-torque detection during entire
(acceleration, steady state,
deceleration) operation, continue
operation after detection.
0
Pr5-22
Over-Torque Detection Level 2
(ot2)
Amp(10
〜
250% of drive’s rated current)
A(150%)
Pr5-23
Over-Torque Detection Time 2 (ot2) 0.0
〜
60.0 Sec
0.1
Pr5-24
{Pr5-21}
Most Recent Fault
Record
0: no fault
16: HPF
(protection circuit
fault)
32: ot2
(Over-Torque2)
0
Pr5-25
{Pr5-22}
2nd Most Recent
Fault Record
1: oC
(over-current)
17: oH1
(IGBT overheat)
33: oL2
(electronic thermal
relay 2)